This tool includes information on commissioning the economizer functionality of
the DDC controller. The instructions below are based on factory default values.
Results may vary depending on the current settings of the unit.

The unit may delay up to three (3) minutes before going into economizer mode.

Commissioning the economizer functionality is done by overriding the outdoor
air and supply air conditions to simulate a scenario in which economizer is used
for cooling. NOTE: Overriding the physical inputs can be dangerous to the
equipment. Use caution when adjusting these values and RESET POWER WHEN
FINISHED!!!

The table below indicates the necessary override values for the corresponding
sensor to simulate economizer. The ‘Supply Temp Source’ can be found on the
‘Supply Temp Set Point’ screen. Navigate to the Analog Inputs Override menu
(Service -> Overrides -> Analog Inputs) and refer to the table below for the
appropriate override value.

In situations where mechanical cooling is available during economizer, increase
the outdoor air temperature to 57.1 F to unlock the cooling.

Economizer Commissioning Tool

Econ Type

Supply

Temp

Source

Outdoor Air

Temp

Cold Coil

Temp

Discharge

Temp

Room Air

Temp

Outdoor

Air Relative

Humidity

Temp Only

Outdoor Air

Reset

53.0ºF

75.0ºF

75.0ºF

-

-

Room Air

Reset

53.0ºF

75.0ºF

75.0ºF

75.0ºF

-

Local/BMS

53.0ºF

75.0ºF

75.0ºF

-

-

Temp and

Dew Point

Outdoor Air

Reset

53.0ºF

75.0ºF

75.0ºF

-

30%

Room Air

Reset

53.0ºF

75.0ºF

75.0ºF

75.0ºF

30%

Local/BMS

53.0ºF

75.0ºF

75.0ºF

-

30%

Analog Input

Outside Temperature

ManualControl B005:

ON

ManualPosition: 57.1

Value 57.1

Service Menu

a. Information

b. Overrides

c. BMS Config

I/O Manual Control

E. Components

A. Analog

B. Digital Inputs

42

DDC Controller for Tempered Air Products

®