G. service – Greenheck Microprocessor Controller (475595 IOM) TAP v2.10 April 2014 (RVE, ERCH-01, ERT-01) User Manual
Page 41

*The BACnet IP/Eth card is configured for DHCP
from the factory.
To view the current parameters, go the BMS Config
menu within the controller by pressing the
Prg
key.
To access the BMS
Config sub-menu, enter
the service password
(Default=1000).
Protocol must be
BACnet IP/Eth and
BACnet Plugin must be
YES.
Press
arrow button to
view next screen.
Current BACnet IP
parameters should be
displayed. If values
appear to be zero, follow
the procedure below.
To read current
parameters:
1. Power on controller and
allow several minutes
to initialize.
2. Go to BMS Config
menu and view BACnet
Read/Write screen.
3. Change Function to
Read and Update? to
YES.
Current BACnet IP
parameters should now
be displayed in the
BACnet TCP/IP SETUP screen. If all values appear
to be zeros, consult the factory. (Make sure you have
allowed several minutes for the controller to initialize).
*Values may appear to be zero prior to setting the
Function to READ.
To change BACnet TCP/IP parameters:
1. Power on the controller and allow several minutes
to initialize.
2. Go to BMS Config menu and view TCP/IP SETUP
screen.
3. Move cursor to desired parameter by pressing the
buttons. Press
to select the parameter
to change. Press the
buttons to adjust the
parameter. Press
to save adjusted value.
4. Once desired parameters have been entered, go
to BACnet Read/Write screen. Change Function to
Write and Update? to YES.
5. Reboot the controller by cycling power to the unit.
Allow several minutes for the controller to initialize.
6. View TCP/IP parameters. If changed values did not
save, contact the factory.
BACnet® IP/Eth Quick Start
BMS Configuration
Protocol: BACnet
IP/Eth
BACnet Plugin?
YES
TCP/IP SETUP
Instance: 77000
IP set by:
DHCP
IP: 128.1.104.134
Subnet: 255.255.000.000
Gatewy: 128.1.0.12
TCP/IP Setup
DNS 1:
193.168.001.001
DNS 2:
193.168.001.001
Type: IP
BACnet Read/Write
Function: Read
Update? Yes
*Cycle unit power to confirm
write command.
G.
Service
c. BMS Config
The communication card
is located in the Serial
Card port on the face of
the controller. The card
includes two sets of LED
lights for communication
troubleshooting.
Status LED: Indicates the status of communication
between the card and controller.
• Quick green-off-green if communication with
controller is ok.
• Slow red-off-red if communication is not established.
Ethernet LED: Indicates the status of communication
with the network. Wait for 40 seconds to determine
status of communication.
• Flashing green, communication is OK.
• Steady red, communications is not established.
Communication Troubleshooting
See Carel Data sheet for more info.
If attempting to communicate with the controller over
BACnet IP/Eth, refer to the card LEDs for system
information.
Status LED slow red blink
• Confirm card is firmly plugged in.
• Confirm BMS Protocol is set to BACnet IP/Eth.
Ethernet LED red on
• Confirm card is connected to the network.
Recalling Factory Parameters
Follow this procedure to revert to factory parameters for
one power cycle. When restarted, the card will resume
using the previous user parameters.
Factory Default IP address: 172.16.0.1
1. With controller off, hold the push button located on
the BACnet IP/Eth card, while powering the controller
back on.
2. Continue to hold the button, while watching the
Status LED. Wait for the Status LED to blink red
slowly, and release before the third slow flash.
3. Wait for about one minute for the factory parameters
to be loaded.
4. Follow the procedure to read the current parameters
to confirm factory defaults have been loaded.
Push Button
Ethernet
LED
Status
LED
MAC address
41
DDC Controller for Tempered Air Products
®