G. service – Greenheck Microprocessor Controller (475595 IOM) TAP v2.10 April 2014 (RVE, ERCH-01, ERT-01) User Manual

Page 41

background image

*The BACnet IP/Eth card is configured for DHCP
from the factory.

To view the current parameters, go the BMS Config
menu within the controller by pressing the

Prg

key.

To access the BMS
Config
sub-menu, enter
the service password
(Default=1000).

Protocol must be
BACnet IP/Eth and
BACnet Plugin must be
YES.

Press

arrow button to

view next screen.

Current BACnet IP
parameters should be
displayed. If values
appear to be zero, follow
the procedure below.

To read current
parameters:

1. Power on controller and

allow several minutes
to initialize.

2. Go to BMS Config

menu and view BACnet
Read/Write screen.

3. Change Function to

Read and Update? to
YES.

Current BACnet IP
parameters should now
be displayed in the

BACnet TCP/IP SETUP screen. If all values appear
to be zeros, consult the factory. (Make sure you have
allowed several minutes for the controller to initialize).
*Values may appear to be zero prior to setting the
Function to READ.

To change BACnet TCP/IP parameters:
1. Power on the controller and allow several minutes

to initialize.

2. Go to BMS Config menu and view TCP/IP SETUP

screen.

3. Move cursor to desired parameter by pressing the

buttons. Press

to select the parameter

to change. Press the

buttons to adjust the

parameter. Press

to save adjusted value.

4. Once desired parameters have been entered, go

to BACnet Read/Write screen. Change Function to
Write and Update? to YES.

5. Reboot the controller by cycling power to the unit.

Allow several minutes for the controller to initialize.

6. View TCP/IP parameters. If changed values did not

save, contact the factory.

BACnet® IP/Eth Quick Start

BMS Configuration

Protocol: BACnet

IP/Eth

BACnet Plugin?

YES

TCP/IP SETUP

Instance: 77000

IP set by:

DHCP

IP: 128.1.104.134
Subnet: 255.255.000.000
Gatewy: 128.1.0.12

TCP/IP Setup

DNS 1:

193.168.001.001

DNS 2:

193.168.001.001

Type: IP

BACnet Read/Write

Function: Read

Update? Yes

*Cycle unit power to confirm
write command.

G.

Service

c. BMS Config

The communication card
is located in the Serial
Card
port on the face of
the controller. The card
includes two sets of LED
lights for communication
troubleshooting.

Status LED: Indicates the status of communication
between the card and controller.
• Quick green-off-green if communication with

controller is ok.

• Slow red-off-red if communication is not established.

Ethernet LED: Indicates the status of communication
with the network. Wait for 40 seconds to determine
status of communication.
• Flashing green, communication is OK.
• Steady red, communications is not established.

Communication Troubleshooting

See Carel Data sheet for more info.

If attempting to communicate with the controller over
BACnet IP/Eth, refer to the card LEDs for system
information.

Status LED slow red blink
• Confirm card is firmly plugged in.
• Confirm BMS Protocol is set to BACnet IP/Eth.

Ethernet LED red on
• Confirm card is connected to the network.

Recalling Factory Parameters

Follow this procedure to revert to factory parameters for
one power cycle. When restarted, the card will resume
using the previous user parameters.

Factory Default IP address: 172.16.0.1

1. With controller off, hold the push button located on

the BACnet IP/Eth card, while powering the controller
back on.

2. Continue to hold the button, while watching the

Status LED. Wait for the Status LED to blink red
slowly, and release before the third slow flash.

3. Wait for about one minute for the factory parameters

to be loaded.

4. Follow the procedure to read the current parameters

to confirm factory defaults have been loaded.

Push Button

Ethernet

LED

Status

LED

MAC address

41