This screen only appears if a heating operation was provided with the unit.

When the Heating Control is in the MANUAL mode, use the arrow buttons to vary
the heating output.

Electric Heater: The Heater Control % is proportional to the 0-10 VDC signal
being sent to the SCR controller, located in the electric heater control center.
0% Heating = 0 VDC - 0 kW output

100% Heating = 10 VDC - Max kW output

Hot Water: The Heater Control % is proportional to the 0-10 VDC signal being
sent to the heating control valve (BY OTHERS).
0% Heating = 0 VDC

100% Heating = 10 VDC

Indirect Gas: The Heater Control % is proportional to the 0-10 VDC signal being
sent to the indirect gas furnace controller, located in the indirect gas control
center. The first stage is on at 1% Heater Control. The furnace will then modulate
proportionally from minimum to maximum capacity. The furnace is subject to
minimum On/Off times and Heating Lockouts.
0% = 0 VDC – OFF
1% = 0 VDC – MINIMUM TURNDOWN ENABLED
1 - 100% = 0 - 10 VDC = FURNACE MODULATION

Heat Pump: The Heating % displays compressor engagement as a percent. The
compressors are subject to the minimum On/Off times and Heating Lockouts.
Compressors engage in sequence as described in the Compressor Staging
screen in the Manufacturer > Factory Settings menu.

Heating Override

Heating

Control:

Auto

Heating:

100%

T

HIS

SCREEN

ALLOWS

THE

USER

TO

OVERRIDE

THE

COOLING

OPERATION

.

This screen only appears if a cooling operation was provided with the unit.

When the Cooling Control is in the MANUAL mode, use the arrow buttons to vary
the cooling output.

Chilled Water: The Cooling % is directly proportional to the 0 - 10 VDC output
signal.
0% Cooling = 0 VDC; 100% Cooling = 10 VDC

Packaged Cooling and Heat Pump: The Cooling % displays compressor
engagement as a percent. The compressors are subject to the minimum
On/Off times and Heating/Cooling Lockouts. Compressors engage in sequence
as described in the Compressor Staging screen in the
Manufacturer > Factory Settings menu.

Cooling Override

Cooling

Control:

Auto

Cooling:

100%

T

HIS

SCREEN

ALLOWS

THE

USER

TO

OVERRIDE

THE

ENERGY

RECOVERY

WHEEL

PREHEATER

.

This screen only appears if an electric preheat frost control was provided with the
unit.

Wheel Preheat Override

Energy Recovery Wheel

Preheat

Control:

Auto

Preheater:

OFF

T

HIS

SCREEN

ALLOWS

THE

USER

TO

OVERRIDE

THE

ENERGY

WHEEL

OPERATION

.

This screen only appears if the unit is equipped with a VFD operated energy wheel.

When the Wheel Control is in the MANUAL mode, use the arrow buttons to alter
the wheel %. This is directly proportional to a 0 - 10 VDC signal being sent to the
energy wheel VFD.

Energy Wheel Override

Wheel Control:

Auto

Wheel:

100%

24

DDC Controller for Tempered Air Products

®