Since the unit is only part of a complete system, the airflow(s) may momentarily
change (ie. If a downstream damper closes). This delay is intended to prevent
false loss of airflow alarms. (Factory Default = 30 seconds)

Fan/Airflow Proving

Alarm delay:

30s

(inputs ID1 & ID5)

T

HIS

SCREEN

ALLOWS

ADJUSTMENT

OF

THE

TIME

DELAY

FOR

WHEEL

ROTATION

ALARM

.

This screen only appears if an energy wheel was provided with the unit.

Similar to the Fan/Airflow Proving Switch alarm, the energy wheel rotation alarm
delay allows time to elapse prior to the controller showing an alarm. The delay
prevents a false alarm from occurring if the sensor does not sense the wheel
rotation for the allotted time.

Wheel Rotation Sensor

Alarm delay:

30s

(input ID3)

T

HIS

SCREEN

ALLOWS

ADJUSTMENT

OF

THE

TIME

DELAY

BEFORE

THE

EXHAUST

FAN

WHEN

THE

SUPPLY

FAN

STARTS

.

This screen only appears if an energy wheel was provided with the unit.

The delay between the starting of supply and exhaust fans reduces the startup
amp draw of the unit. The exhaust fan engages first, allowing the energy wheel to
see space temperature conditions prior to the supply fan engaging. This allows
the wheel to provide maximum preconditioning of the outdoor air. This also
minimizes the potential of extreme outdoor air temperatures being supplied to the
space, prior to the cooling or heating engaging.

Fan Delay

Time delay between starting
of supply & exhaust fans.
Fan delay:

15s

T

HIS

SCREEN

ALLOWS

ADJUSTMENT

OF

THE

FAN

START

DELAY

.

This timer allows the damper time to open before the fan start sequence begins.
This prevents the fans from having to overcome higher static pressure when the
damper(s) are opening. (Factory Default = 10 seconds)

Damper Setup

Allow the dampers to open
for: 10 seconds before
starting the fans.

T

HIS

SCREEN

DISPLAYS

ADDITIONAL

PARAMETERS

THAT

MAY

BE

USED

DURING

UNOCCUPIED

FAN

CYCLING

.

After the unoccupied heating set point has been satisfied, the supply fan will
continue to run for the Heat Off Delay.

On 100%OA MUA units, the OA damper can be configured to open to allow
unoccupied fan cycling.

Unoccupied Mode Setup

Type:

Cycle Supply Fan

Source: Input

ID6

Heat Off Delay:

60s

Open OA damper during
unocc cycle?:

NO

T

HIS

SCREEN

ALLOWS

THE

USER

TO

CHANGE

THE

TEMPORARY

OCCUPANCY

OVERRIDE

CONTACT

FROM

M

OMENTARY

TO

M

AINTAINED

.

The default temporary occupancy override functionality is a momentary contact
at ID6 that will override unoccupied mode for a user adjustable 1, 2, or 3 hours.
This screen allows the user to change the setting and allow the unit to override
unoccupied mode as long as the contact at ID6 is closed. This works well in
application that have a motion detector, rotary timers, etc.

Unocc Override Setup

Contact: Momentary

33