beautypg.com

Troubleshooting ntc temperature sensor chart – Greenheck Microprocessor Controller (475595 IOM) TAP v2.10 April 2014 (RVE, ERCH-01, ERT-01) User Manual

Page 39

background image

Display is hard to read.

Unit Controller Display: Hold

Esc

ESC and

ENTER at the same time, while

pressing

DOWN or

UP to adjust display contrast.

Remote Display: Hold

ALARM,

Prg

PRG, and

Esc

ESC at the same time, while

pressing

DOWN or

UP to adjust display contrast.

Remote display panel
displays “NO LINK” or is
blank.

Hold

DOWN,

UP and

ENTER for 4 seconds. Set the display address to 32.

The display requires a standard 24 AWG six conductor phone cable connected to the
unit controller.

Red alarm button is
flashing.

Press the

ALARM button to review and clear unit alarms. Enter the DATA

LOGGER menu to view previous alarms.

Controller resets itself or
is not on.

Check the supply voltage to the controller at terminals G-G0. The board requires
24VAC. Check the 24VAC transformer in the unit control center.

Menus are locked with a
password.

The factory default Manufacturer Password = 1000.
The factory default Service Password = 1000.

Temperature sensor
failure.

Check the analog input terminal block (labeled terminals B1, B2, B3, etc) for loose
wires. Disconnect temperature sensors to check sensor resistance.

Troubleshooting

NTC Temperature Sensor Chart

120

110

100

90

80

70

60

50

40

30

20

10

0

4 6 8 10 12 14 16 18 20 22 24 26 28

T

emperatur

e (ºF)

Resistance (k

:)

39