Greenheck Microprocessor Controller (475595 IOM) TAP v2.10 April 2014 (RVE, ERCH-01, ERT-01) User Manual

Page 18

background image

T

HIS

SCREEN

DISPLAYS

THE

SUPPLY

FAN

SPEED

SET

POINTS

.

This screen only appears if equipped with a supply fan VFD controlled by
microprocessor.

The Speed Set Point is the proportional percentage of the analog output from the
controller to the VFD.

0% Speed = Min Speed (determined by VFD)
100% Speed = Max Speed (determined by VFD)

UnOccupied Cycle - The supply fan speed when the unit is on during unoccupied
cycle times.

Possible Set Point Sources:

Local – The fan speed will be constant set from screen (exp. 100%).

BMS – The BMS can directly control the fan speed (requires BMS communication
option).

Duct Pressure – Fan speed is determined by duct pressure control loop.

Building Pressure - Fan speed is determined by building pressure control loop.

CO2 - Fan speed is determined by CO2 control loop.

Supply Fan Speed SetPt

Active:

100%

Source: Local

100%

UnOccupied Cycle 100%

(0%=Min Speed by VFD)

T

HIS

SCREEN

DISPLAYS

THE

ROOM

SET

POINTS

DURING

THE

UNOCCUPIED

MODE

.

This screen only appears if an unoccupied recirculation damper was provided with
the unit. Room sensor(s) must be wired to the controller.

In the unoccupied mode, the unit will monitor the room temperature and humidity
sensors. The unit will cycle on to maintain the unoccupied room set points by
tempering recirculated air. The differential prevents short cycling. For example, in
heating, the unit cycles on at 60°F and turns off at 65°F.

UnOcc Fan Cycle Setup

UnOcc Room Set Points:
Heating:

65.0°F

Cooling:

80.0°F

Room

RH:

50.0%

Temp

Diff:

5.0°F

Dehumid Diff:

5.0%

T

HIS

SCREEN

DISPLAYS

THE

TEMPERATURE

AT

WHICH

THE

UNIT

WILL

ENABLE

FROST

CONTROL

MODE

IF

NECESSARY

. (F

ACTORY

D

EFAULT

= 5°F)

This screen only appears if the unit has an energy recovery wheel and a frost
control method was provided with the unit.

Upon sensing a high differential pressure across the energy wheel, the unit will go
into defrost if the outside air temperature is below this temperature setting.

Defrost

Allow wheel defrost
mode when outside
is below:

05.0°F

18

DDC Controller for Tempered Air Products

®