Main menu overview – Greenheck Microprocessor Controller (475595 IOM) TAP v2.10 April 2014 (RVE, ERCH-01, ERT-01) User Manual

Page 12

background image

The microprocessor controller will revert to a default main menu loop. This loop includes several screens to view the
operating conditions of the unit. Scroll through the menu screens by using the

keys. Screens with a dashed

line border are dependent upon an optional accessory and may not always appear.

Main Menu Overview

T

HE

S

ENSOR

S

TATUS

SCREEN

DISPLAYS

REAL

TIME

CONDITIONS

FROM

THE

SENSORS

LOCATED

IN

THE

UNIT

AND

THE

ROOM

(

IF

INSTALLED

).

TIME DATE UNIT##

Supply Air:

000.0°F

Outside Air:

000.0°F

OA Humidity

00.0%

Cold Coil:

000.0°F

Room Temp:

000.0°F

Room Humidity:

00.0%

STATUS LINE

O

CCUPANCY

O

VERRIDE

(

IF

U

NOCCUPIED

)

If the unit is currently unoccupied, the occupancy can be temporarily overridden
for a period of Override Time. The Override Time parameter can be set from one
to three hours.

Occupancy Override

Clock Override:

OFF

Override Time:

1 hr

TIME DATE UNIT##

TAP v2.10 GWY1X000XXXX
STATUS LINE

®

T

HE

INITIAL

MENU

SCREEN

DISPLAYS

THE

PROGRAM

VERSION

,

UNIT

CODE

AND

STATUS

LINE

. T

HE

STATUS

LINE

DISPLAYS

WHICH

MODE

THE

UNIT

IS

IN

.

Possible modes include:

• Initial Delay
• Opening Dampers
• Exhaust Fan Starting
• Supply Fan Starting
• System On
• Defrost Mode Active
• Sys On - Econ+Cooling
• Sys On - Economizer
• Sys On - Heating
• Sys On - Cooling
• Sys On - Dehumidifying
• Sys On - Dehumid & Reheat

• Unoccupied - Unit On
• Unoccupied - Unit Off
• Unoccupied - Dehumid
• Unoccupied - Dehumid & Reheat
• Unoccupied - Heating
• Unoccupied - Cooling
• Manual Override
• Remote Off
• Press Alarm Button!!!
• Temp Occupied

S

UPPLY

F

AN

S

TATUS

. (

IF

EQUIPPED

WITH

VFD)

If equipped with a supply fan VFD, this screen will display the supply fan ramp
being sent from the controller to the VFD. The minimum and maximum speeds are
set in the VFD (See unit Installation and Operation Manual for VFD programming).
The controller can modulate the fan between the min and max speeds via an
analog output. This screen also displays the method of fan control and the
parameter it is controlling.

Possible methods include: Constant Speed, Duct Pressure Control, Building
Pressure Control, CO2 Control, and Single Zone VAV.

Supply Fan Status

Supply Fan Ramp:

0%

(0%=Min Speed by VFD)

Duct Ps Control
Duct Pressure:

0.00”wc

STATUS LINE

E

XHAUST

F

AN

S

TATUS

. (

IF

EQUIPPED

WITH

VFD)

If equipped with an exhaust fan VFD, this screen will display the exhaust fan ramp
being sent from the controller to the VFD. The minimum and maximum speeds are
set in the VFD (See unit Installation and Operation Manual for VFD programming).
The controller can modulate the fan between the min and max speeds via an
analog output. This screen also displays the method of fan control and the
parameter it is controlling.

Possible methods include: Constant Speed, Building Pressure Control, Outdoor
Air Damper Tracking, and Supply Fan Tracking.

Exhaust Fan Status

Exhaust Fan Ramp:

0%

(0%=Min Speed by VFD)

Building Ps Control
Building Ps:

+.000”wc

STATUS LINE

E

NERGY

R

ECOVERY

W

HEEL

S

TATUS

. (

IF

EQUIPPED

)

If selected with a preheater, the status will also be displayed.

Energy Recovery

Wheel: 100%

Speed

Wheel Differential
Pressure Is:

Normal

Preheater: OFF

STATUS LINE

12

DDC Controller for Tempered Air Products

®