This is an example of an analog input configuration screen.

In the I/O configuration screens, the user can alter the physical location and type
of each point.

Similar configuration screens appear for the remaining I/O.

Analog Input

Outside Temperature
En: ON

Ch: B005

Normal NTC

Offset: 0.0°F
Value: 70.5°F

Alarm Time Delay

Outside Temperature
Input B0005:

73.5°F

Out of Range Alarm

Power Delay:

30s

Run Delay:

30s

Units: Temperature

Digital Input

Remote On/Off
Enable: ON Channel:

4

Action: CLOSED
Delay: 0s
Status: Closed

Analog Output Config

Cool:
Enable: Yes
Channel: 3
Action: DIRECT

Minimum: 0.0vdc
Maximum: 10.0vdc

Relay Output

Defrost
Enable: Yes
Channel: 1
Status: OFF

The I/O Configuration menu allows adjustment of all controller inputs and outputs.
This menu is similar to the Probe Adjustment menu, except that it additionally allows
adjustment of the factory default ‘normal’ states of the digital inputs and the direction
of the analog outputs. Additionally, it allows adjustment of the physical location
of each I/O. ADJUSTMENT OF I/O PHYSICAL LOCATION MUST ONLY BE DONE
UNDER FACTORY GUIDANCE! IMPROPER ADJUSTMENT MAY RESULT IN SYSTEM
DAMAGE!

H.

Manufacturer

b. I/O Configuration

T

HIS

SCREEN

ALLOWS

THE

ADJUSTMENT

OF

THE

ECONOMIZER

FUNCTION

.

This screen only appears if an economizer mode was selected with the unit.

If the unit was selected with cooling and economizer, the user has the option to
allow mechanical cooling during the economizer mode.

If the unit is equipped with an energy wheel and bypass dampers, the bypass
dampers will open and the energy wheel will turn off once the modulating outdoor
air dampers have opened more than the offset.

Economizer Controller

Allow mechanical cooling
during econ?

Yes

Wheel/Bypass Damper:

Offset from minOA:

5%

Hysteresis: 3%

The Factory Settings menu allows adjustment of parameters that are critical for
proper unit operation. Adjustment of these parameters is only recommended with
factory guidance. To access the Factory Settings menu, enter the manufacturer
password (Default=1000).

H.

Manufacturer

c. Factory Settings

T

HIS

SCREEN

ALLOWS

THE

USER

TO

DISABLE

THE

EXHAUST

FAN

EXCEPT

IN

ECONOMIZER

MODE

This screen only appears if economizer mode is selected, the unit has
recirculation, and the exhaust fan is tracking the outdoor air dampers.

This functionality allows the exhaust fan to track the outdoor air damper only
during economizer mode.

Disable Exhaust Fan

Exhaust fan available
only during econ mode?


No

29