This screen only appears if the selected BMS protocol is set to BACnet IP/Eth and
BACnet Plugin = YES.

If a BACnet IP card has been installed, the default parameters can be changed
via the controller display. The card is in DHCP mode from the factory. Once
communication is established, the user can enter static IP parameters.

To view current parameters:
1. Power on controller and allow several minutes to initialize.
2. Go to BMS Config menu and view BACnet Read/Write screen.
3. Change Function to Read and Update? to YES.

TCP/IP SETUP

Instance: 77000

IP set by:

DHCP

IP: 128.2.104.134
Subnet: 255.255.000.000
Gatewy: 128.2.0.12

TCP/IP SETUP

DNS 1:

193.168.001.001

DNS 2:

193.168.001.001

Type: IP

T

HIS

SCREEN

ALLOWS

THE

USER

TO

ADJUST

BAC

NET

MSTP

PARAMETERS

.

This screen only appears if the selected BMS protocol is set to BACnet MSTP and
BACnet Plugin = YES.

If a BACnet MSTP card has been installed, the default parameters can be
changed via the controller display. Factory settings are shown in the screen to the
left.

To view current parameters:
1. Power on controller and allow several minutes to initialize.
2. Go to BMS Config menu and view BACnet Read/Write screen.
3. Change Function to Read and Update? to YES.

Current BACnet MSTP parameters should now be displayed in the BACnet MSTP
SETUP screen. If all values appear to be zeros, consult the factory. (Make sure
you have allowed several minutes for the controller to initialize). *Values may
appear to be zero prior to setting the Function to READ.

To change BACnet MSTP parameters:
1. Power on controller and allow several minutes to initialize.
2. Go to BMS Config menu and view MSTP SETUP screen.
3. Move cursor to desired parameter by pressing the

buttons. Press

to select the parameter to change. Press the

buttons to adjust the

parameter. Press

to save adjusted value.

4. Once desired parameters have been entered, go to BACnet Read/Write

screen. Change Function to Write and Update? to YES.

5. Reboot the controller by cycling power to the unit. Allow several minutes for

the controller to initialize.

6. View MSTP parameters. If changed values did not save, contact the factory.

MSTP SETUP

Instance: 77000

Baudrate 38400
MAC Addr:

0

MaxMasters: 127
MaxInfoFrames: 20

BACnet Read/Write

Function: Read

Update? Yes

*Cycle unit power to confirm
write command.

T

HIS

SCREEN

ALLOWS

THE

USER

TO

ADJUST

M

ODBUS

PARAMETERS

.

This screen only appears if the selected BMS protocol is set to Modbus

.

The address is the Modbus address of the card installed in the SERIAL CARD
port located on the face of the controller. (Factory Default Address = 1).

MODBUS SETUP

Address: 1

Baudrate 9600

Stop bit:

2

Parity mode:

NONE

T

HIS

SCREEN

ALLOWS

THE

USER

TO

SELECT

THE

BMS

PROTOCOL

. A

LL

BMS

PROTOCOLS

REQUIRE

A

COMMUNICATIONS

CARD

INSTALLED

IN

THE

SERIAL CARD

PORT

,

LOCATED

ON

THE

FACE

OF

THE

CONTROLLER

.

If the protocol is BACnet MSTP or BACnet IP/Eth, the user can change common
BACnet parameters via the controller. The BACnet Plugin must be set to YES.

BMS Configuration

Protocol: BACnet

MSTP

BACnet Plugin?

YES

The BMS Config menu allows the user to view and alter BMS protocol settings.
If the BMS protocol is BACnet or Modbus, additional screens allow further
configuration. See below for details. To access the BMS Config sub-menu, enter
the service password (Default=1000).