Greenheck Microprocessor Controller (475595 IOM) TAP v2.10 April 2014 (RVE, ERCH-01, ERT-01) User Manual
Page 4

Economizer
If the application requires cooling, and the outdoor 
air conditions are suitable for free cooling, the 
controller may enter the economizer state. If the unit is 
economizing and the discharge temperature set point is 
not being met, the controller may bring on mechanical 
cooling. If equipped with a modulating outdoor air and 
recirculated air damper, the dampers will modulate 
between the minimum OA and maximum positions to 
maintain the supply temperature set point. If equipped 
with an energy wheel, see Energy Recovery Wheel 
Sequence.
• Temperature: The economizer will be locked out
when:
- The outside air is less than the economizer low
lockout (40°F).
- The outside air is greater than the economizer
high lockout (65°F).
-
The unit is operating in dehumidification mode.
-
There is a call for heating.
• Temperature/Dew Point: The economizer will be
locked out when:
- The outside air is less than the economizer low
lockout (40°F dry-bulb).
- The outside air is greater than the economizer
high lockout (75°F dry-bulb).
- The outside air is greater than the economizer
high dew point lockout (55°F dew point)
-
The unit is operating in dehumidification mode.
-
There is a call for heating.
Dehumidification
The cooling is controlled to maintain the cold coil set 
point. The dehumidification sequence will be locked out 
when the OA is less than the dehumidification lockout 
(10°F) above the cold coil set point. If equipped with 
BMS communications, the user can also directly set the 
cold coil leaving air set point.
• Optional Room Dehumidistat: The room
dehumidistat is a field mounted sensor that monitors 
the relative humidity (RH) of the room. If the RH 
exceeds set point, the dehumidistat will reset the 
cold coil set point to the minimum (50°F). Once the 
room dehumidistat is satisfied, the cold coil set point 
will return to the maximum (55°F).
• Optional Room Relative Humidity Sensor: The
controller will adjust the cold coil leaving air 
temperature set point between the minimum (50°F) 
and maximum (55°F) set points, to satisfy the desired 
room relative humidity set point.
Reheat
While the unit is in dehumidification mode, the supply 
air can be reheated via Primary Heating Source, On/Off 
Hot Gas Reheat or Modulating Hot Gas Reheat.
• Primary Heating Source: The main heating source
is enabled to reheat the air to meet the supply 
temperature set point. (Except heat pump). The 
primary heat source may also be configured to act as 
secondary reheat.
• Modulating Hot Gas Reheat (bypass damper): The
microprocessor controller will open the On/Off hot 
gas reheat valve, and modulate the Hot Gas Reheat 
bypass damper to maintain the supply temperature 
set point.
• Modulating Hot Gas Reheat (valve): The
microprocessor controller will modulate the hot gas 
reheat valve to maintain the supply temperature set 
point.
• On/Off Hot Gas Reheat: The microprocessor
controller will open the On/Off hot gas reheat valve to 
maintain the supply temperature set point.
Supply Fan VFD Sequence
If the factory has installed a VFD and wired it to the 
controller, it is intended to operate at a constant speed 
during operation. This speed needs to be set during 
test and balance of the unit. If equipped with BMS 
communications, the user can also directly command 
the supply fan speed.
• Optional Room CO2 Sensor: The controller will
modulate the supply fan based upon a comparison 
of the CO2 set point to the actual CO2 levels 
reported from the sensor. Mechanical high static 
protection cutoffs must be installed by others 
to protect the system and equipment from 
over-pressurization.
• Optional Duct Static Pressure Sensor: The
controller will modulate the supply fan based upon a 
comparison of the duct static pressure set point to 
the actual duct static pressure level reported from 
the sensor. Mechanical high static protection 
cutoffs must be installed by others to protect 
the system and equipment from over-
pressurization. The manufacturer does not 
assume responsibility for this.
• Optional Building Static Pressure Sensor: The
controller will modulate the supply fan based upon a 
comparison of the building static pressure set point 
to the actual building static pressure level reported 
from the sensor.
• Optional Single Zone VAV (SZ): The controller will
control the supply air temperature and supply fan 
speed to maintain the room temperature set point. 
This sequence requires a room temperature sensor. 
 
Heating - When the room requires heating, the
controller will reset the supply air temperature set 
point up to the maximum (90°F) while increasing the 
supply fan speed up to its maximum heating speed. 
 
Cooling - When the room requires cooling, the
controller will first reset the supply air temperature 
set point down to the minimum (55°F) while the 
supply fan remains at the minimum cooling speed. 
After a time delay, the supply fan speed will increase 
up to its maximum cooling speed to maintain the 
room temperature set point.
4
DDC Controller for Tempered Air Products
®
