F. Board

Switch

The Board Switch menu allows the user to jump between different controllers with
a remote display. This requires a remote display, along with additional controllers,
set-up in a pLAN network. A pLAN can consist of up to 32 devices, in different
combinations, but a maximum of 31 controllers.

W

HEN

VIEWING

THIS

SCREEN

FROM

A

REMOTE

DISPLAY

,

THE

USER

IS

ABLE

TO

CHANGE

WHICH

CONTROLLER

S

MENU

SHOULD

BE

DISPLAYED

.

Unit Address: The pLAN address of the controller the display is currently
accessing.

Switch to unit: The pLAN address of the controller the display would like to
access.

Board Switch

Unit Address:

1

Switch to unit:

1

1 . . . . . . . . . . 16

17 . . . . . . . . . 32

To manually override a control loop, the unit must be ON. In each respective
screen, change the control from AUTO to MANUAL.

To resume normal operation after overriding the controller, simply cycle power to
the unit.

Control Loop Overrides

Unit must be ON.

To resume normal operation,
cycle unit power.

T

HIS

SCREEN

ALLOWS

THE

USER

TO

OVERRIDE

THE

ENERGY

WHEEL

OPERATION

.

This screen only appears if the unit is equipped with a non-VFD operated energy
wheel.

When the Wheel Control is in the MANUAL mode, use the arrow buttons to turn
the wheel ON or OFF.

Energy Wheel Override

Wheel Control:

Auto

Wheel: OFF

The Overrides menu is for start-up, commissioning and troubleshooting. This
menu allows the user to override the control loops and specific inputs and
outputs. To access the Overrides sub-menus, enter the service password
(Default=1000). Caution: overriding components and I/O can be dangerous to the
equipment. Always cycle power to the unit when finished with the override.

G.

Service

b. Overrides

a. Analog Inputs

b. Digital Inputs

c. Relay Outputs

d. Analog Outputs

e. Control Loops

Code: Controller setup code determines functionality of program. When
contacting the factory, please reference this code.

Ver: Displays the current program version and data code of the current program.

Manual: The manufacturer part number for the corresponding Installation,
Operation and Maintenance (IOM) Manual.

Information

Greenheck Fan

Code: GWY1X000XXXX
Ver.2.10 4/1/14
Manual: 475595
Bios:

5.18 11/17/10

Boot:

4.03 07/03/06

G. Service

The Service menu allows the user to access several sub-menus regarding controller
information, controller overrides, operating hours, BMS configuration, I/O manual
management and Probe Adjustment. The user can also change the default Service
Password (1000) by accessing the Service Settings sub-menu. By accessing the
BMS Config sub-menu, the user can adjust BMS protocol settings. (BACnet®,
LonWorks®, Modbus®)

E

NTERING

THE

I

NFORMATION

SUB

-

MENU

WILL

DISPLAY

INFORMATION

ABOUT

THE

CONTROLLER

AND

THE

PROGRAM

LOADED

ON

THE

CONTROLLER

.

G.

Service

a. Information

Analog Input

Outside Temperature

Manual Control B005:

OFF

Manual Position

0.0

Value

73.5

T

HIS

SCREEN

IS

AN

EXAMPLE

OF

A

MANUALLY

MANAGED

TEMPERATURE

ANALOG

INPUT

.

To manually control an analog input, change Manual Control to ON. Move cursor
to Manual position and alter value. The altered value will be displayed below.

Similar screens exist for the remaining I/O. To resume normal operation, simply
cycle power to the unit. Contact the factory for more details.

23

DDC Controller for Tempered Air Products

®