Greenheck Microprocessor Controller (475595 IOM) TAP v2.10 April 2014 (RVE, ERCH-01, ERT-01) User Manual

Page 31

background image

T

HIS

SCREEN

ALLOWS

THE

USER

TO

ENABLE

THE

HEATER

TO

PROVIDE

REHEAT

IN

ADDITION

TO

HOT

GAS

REHEAT

This screen appears if hot gas reheat and a heating option was provided (except
heat pump).

Setting the heater parameter to enable allows the heating option to provide
additional reheat beyond what the hot gas reheat can provide. This would
typically only be used if the supply air temperature is too cold.

Heater Reheat 2

Will heater be used for reheat
along with hot gas?
Heater: Disable

T

HIS

SCREEN

DISPLAYS

WHEN

EACH

COMPRESSOR

IN

A

SINGLE

OR

DUAL

STAGE

DX

UNIT

WILL

ENGAGE

/

DISENGAGE

.

This screen only appears if DX cooling was provided with the unit.

Each compressor will engage and disengage based upon the percentage of
cooling capacity the controller needs.

Compressor Staging

Stage1: ON @ 50% OFF 0%
Stage2: ON @ 100% OFF

50%

T

HIS

SCREEN

ALLOWS

ADJUSTMENT

OF

THE

H

EATING

PI

CONTROL

LOOP

.

This screen only appears if heating option was provided with the unit.

The controller utilizes a PI loop control for heating. This allows for less sporadic
changes in supply temperature, resulting in a smooth reaction to changing
conditions. To speed up reaction time, decrease the integration time. For slower
reaction time, increase the integration time. When making adjustments, make
them in small increments and test the system to determine if the new setting is
adequate prior to further adjustment. The band is the range that the integration
will occur between. The off delay allows the heating output to temporarily
overshoot the setpoint without dropping the call for heat to prevent unwanted
cycling.

Heater Controller

Integration: 300s
Band: 60°F

Off Delay:

60s

T

HIS

SCREEN

ALLOWS

THE

USER

TO

ENABLE

THE

HEATER

FOR

REHEAT

PURPOSES

.

This screen appears if a heating option was provided and the unit does NOT have
hot gas reheat OR a heat pump.

If it is desired that the heater be used to reheat the air off of the cooling coil when in
dehumidification, adjust this screen so the heater is ENABLED for reheat.

Heater Reheat

Will heater be used for reheat
during dehumidification?
Reheat: Disable

T

HIS

SCREEN

DISPLAYS

THE

COMPRESSOR

MINIMUM

ON

AND

OFF

TIMES

.

This screen only appears if DX cooling was provided with the unit.

The compressor minimum ON/OFF times prevents short cycling of the
compressors.

Compressor Timers

Minimum ON:

30s

Minimum OFF:

180s

Between Stages:

30s

31

DDC Controller for Tempered Air Products

®