Points list • modbus / bacnet – Greenheck Microprocessor Controller (475595 IOM) TAP v2.10 April 2014 (RVE, ERCH-01, ERT-01) User Manual
Page 37

Points List • Modbus / BACnet®
Type
BACnet Device Instance: 77000 (default)
Analog = AV, Integer = AV, Digital = BV
Modbus
Address: 1
Read
Write
Description
Instance
Name
Units
Register
Analog
1
Outside_Air_Temp
°F
40002
R
Outdoor Air Temp (###.#°F)
Analog
2
Supply_Air_Temp
°F
40003
R
Supply Air Temp (###.#°F)
Analog
3
Cold_Coil_Leaving_Temp
°F
40004
R
Cold Coil Temp (###.#°F)
Analog
4
Room_Air_Temp
°F
40005
R
Room AirTemp (if installed) (###.#°F)
Analog
5
Outside_Humidity
percent
40006
R
Outdoor Relative Humidity (###.#%)
Analog
6
Room_Humidity
percent
40007
R
Room Relative Humidity (###.#%)
Analog
11
Temp_Set_Point
°F
40012
R/W
Temperature SetPt (read/write) (###.#F) (See Set Point Menu)
Analog
12
Active_Temp_Set_Point
°F
40013
R
Active Temperature Set Point (###.#F)
Analog
13
Dehumid_Set_Point
percent
40014
R/W
Dehumidification SetPt (read/write) (##.#F, ##.#%) (See Set Point Menu)
Integer
1001
Unit_Status_Index
no-units
40210
R
Note 1 (See below)
Integer
1002
Heating_Control_Loop
percent
40211
R
Heater output (0-100%)
Integer
1003
Cooling_Control_Loop
percent
40212
R
Cooling output (0-100%)
Integer
1004
Energy_Wheel_Speed
percent
40213
R
Energy recovery wheel speed (0-100%)
Integer
1005
Reheat_Control_Loop
percent
40214
R
Hot gas reheat output (0-100%)
Integer
1006
CO2_Level
ppm
40215
R
CO2 Levels (ppm)
Integer
1007
CO2_Set_Point
ppm
40216
R/W
CO2 Set Point (ppm)
Integer
1008
Supply_VFD_Speed
percent
40217
R
Supply Fan VFD Speed (0-100%)
Integer
1009
Supply_VFD_SetPt
percent
40218
R/W
Supply Fan VFD Set Point (0-100%)
Integer
1010
Exhaust_VFD_Speed
percent
40219
R
Exhaust Fan VFD Speed (0-100%)
Integer
1011
Exhaust_VFD_SetPt
percent
40220
R/W
Exhaust Fan VFD Set Point (0-100%)
Integer
1012
OA_Damper_Position
percent
40221
R
Outdoor Damper Position (0-100%)
Integer
1013
OA_Damper_SetPt
percent
40222
R/W
Minimum OA Damper Position (0-100%)
Integer
1014
Duct_Pressure
no-units
40223
R
Supply Duct Pressure (#.##"WC)
Integer
1015
Duct_Pressure_SetPt
no-units
40224
R/W
Supply Duct Pressure Set Point (value/100=#.##" WC)
Integer
1016
Building_Pressure
no-units
40225
R
Building Pressure (value/1000 = 0.###" WC)
Integer
1017
Building_Pressure_SetPt
no-units
40226
R/W
Building Pressure Set Point (value/1000 = 0.###" WC)
Inactive_Text
Active_Text
Digital
1
On_Off_Stat
Off
On
10002
R
Unit ON/OFF status
Digital
2
Supply_Fan_Status
Off
On
10003
R
Supply fan status
Digital
3
Exhaust_Fan_Status
Off
On
10004
R
Exhaust fan status
Digital
4
Occupancy_Status
Unoccupied
Occupied
10005
R
Occupancy Status (0=Unoccupied, 1=Occupied)
Digital
5
Stage_Compressor1_
Status
Off
On
10006
R
Stage Compressor #1 status
Digital
6
Stage_Compressor2_
Status
Off
On
10007
R
Stage Compressor #2 status
Digital
7
Defrost_Mode
Off
On
10008
R
Defrost mode status
Digital
8
Digital_Scroll_Status
Off
On
10009
R
Digital Scroll status
Digital
10
Unit_Start_Stop
Stop
Start
10011
R/W
Unit start/stop command
Digital
11
Reset_Alarms
Don't Reset
Reset Alarms
10012
R/W
Reset alarms command
Digital
12
Occupied_Unoccupied
Occupied
Unoccupied
10013
R/W
Occupied/unoccupied command (0=occupied, 1=unoccupied)
Digital
20
Global_Alarm
Off
Alarm
10021
R
Global alarm indication (active when there is at least one alarm)
Digital
21
Supply_air_proving
Off
Alarm
10022
R
Supply airflow proving alarm
Digital
22
High_Wheel_Pressure
Off
Alarm
10023
R
High wheel pressure (high airflow or dirty wheel)
Digital
23
Wheel_Rotation
Off
Alarm
10024
R
Wheel rotation alarm
Digital
24
Exhaust_air_proving
Off
Alarm
10025
R
Exhaust airflow proving alarm
Digital
25
Dirty_filter
Off
Alarm
10026
R
Dirty filter alarm
Digital
26
Compressor_trip
Off
Alarm
10027
R
Compressor trip alarm
Digital
27
Supply_air_low_limit
Off
Alarm
10028
R
Supply air temperature low limit alarm
Digital
28
Sensor1_out_of_range
Off
Alarm
10029
R
Sensor#1 out of range (outside air temperature)
Digital
29
Sensor2_out_of_range
Off
Alarm
10030
R
Sensor#2 out of range (supply air temperature)
Digital
30
Sensor3_out_of_range
Off
Alarm
10031
R
Sensor#3 out of range (cold coil leaving air temperature)
Digital
31
Sensor4_out_of_range
Off
Alarm
10032
R
Sensor#4 out of range (room temperature)
Digital
32
Sensor5_out_of_range
Off
Alarm
10033
R
Sensor#5 out of range (room humidity)
Digital
33
Sensor6_out_of_range
Off
Alarm
10034
R
Sensor#6 out of range (outdoor humidity)
Digital
34
Sensor7_out_of_range
Off
Alarm
10035
R
Sensor#7 out of range (building pressure sensor)
Digital
35
Sensor8_out_of_range
Off
Alarm
10036
R
Sensor#8 out of range (duct pressure sensor)
Digital
36
Sensor9_out_of_range
Off
Alarm
10037
R
Sensor#9 out of range (CO2 sensor)
Digital
37
Sensor10_out_of_range
Off
Alarm
10038
R
Sensor#10 out of range (auxiliary temp)
pCOe Expansion Board Variables (Requires pCOe)
Analog
21
Aux_AI1
°F or Percent
40022
R
pCOe Analog Input Probe Value 1
Analog
22
Aux_AI2
°F or Percent
40023
R
pCOe Analog Input Probe Value 2
Analog
23
Aux_AI3
°F or Percent
40024
R
pCOe Analog Input Probe Value 3
Analog
24
Aux_AI4
°F or Percent
40025
R
pCOe Analog Input Probe Value 4
Analog
25
Aux_AO1
percent
40026
R/W
pCOe Auxiliary Analog Out (0-10V)
Digital
51
Aux_DI1
Off
On
10052
R
pCOe Auxiliary Digital Input1
Digital
52
Aux_DI2
Off
On
10053
R
pCOe Auxiliary Digital Input2
Digital
53
Aux_DI3
Off
On
10054
R
pCOe Auxiliary Digital Input3
Digital
54
Aux_DI4
Off
On
10055
R
pCOe Auxiliary Digital Input4
Digital
55
Aux_DO1
Off
On
10056
R/W
pCOe Auxiliary Digital Output1
Digital
56
Aux_DO2
Off
On
10057
R/W
pCOe Auxiliary Digital Output2
Digital
57
Aux_DO3
Off
On
10058
R/W
pCOe Auxiliary Digital Output3
Digital
58
Aux_DO4
Off
On
10059
R/W
pCOe Auxiliary Digital Output4
Unit Status Index
0 System Off
5 System On
10 System On - Economizer & Cooling
15 Unoccupied - Heating
20 Remote off
1 Initial Delay
6 Defrost Mode Active
11 System On - Dehumidifying
16 Unoccupied - Cooling
21 Alarm
2 Opening Dampers
7 System On - Economizer
12 System On - Dehumidifying & Reheat
17 Unoccupied -Dehumidifying
22 Temp Occupied
3 Exhaust Fan Starting
8 System On - Heating
13 Unoccupied - Unit off
18 Unoccupied -Dehumid&Reheat
4 Supply Fan Starting
9 System On - Cooling
14 Unoccupied - Unit on
19 Manual Override
37