Greenheck Microprocessor Controller (475595 IOM) TAP v2.10 April 2014 (RVE, ERCH-01, ERT-01) User Manual

Page 30

background image

T

HIS

SCREEN

DISPLAYS

THE

DIGITAL

SCROLL

COMPRESSOR

PARAMETERS

.

This screen only appears if a digital scroll compressor was provided with the unit.

Minimum OFF: This is the minimum voltage the controller outputs when the
digital scroll is disabled/OFF

Minimum ON: This is the minimum voltage the controller outputs when the digital
scroll is enabled/ON.

Maximum: This is the maximum voltage the controller outputs when the digital
scroll is operating at full capacity.

Delay OFF: Delays shutting off digital scroll by this duration.

Max Power Start: Upon starting, the digital scroll will run at full capacity for this
duration. This ensures the refrigeration system is at proper conditions, prior to
modulation.

Digital Compressor

Minimum OFF:

1.0vdc

Minimum ON:

1.9vdc

Maximum: 5.0vdc

Delay OFF:

60s

Max Power Start:

120s

T

HIS

SCREEN

DISPLAYS

THE

NUMBER

OF

STANDARD

COMPRESSOR

STAGES

PROVIDED

WITH

THE

UNIT

AND

SHOWS

THE

ROTATION

SEQUENCE

.

This screen only appears if DX cooling was provided with the unit.

The number of stages displayed is equal to the number of non-modulating
compressors. Factory default compressor rotation is LIFO (Last In, First Out).
Compressor rotation can not be changed on units equipped with: Digital Scrolls,
Hot Gas Reheat or Heat Pump.

Compressor Setup

# of stages:

2

Rotation: LIFO

T

HIS

SCREEN

ALLOWS

THE

ADJUSTMENT

OF

THE

COLD

COIL

FREEZE

-

UP

PROTECTION

PARAMETERS

.

This screen only appears if DX cooling was provided with the unit.

This sequence protects the evaporator coil from freezing up in cooling mode
when the discharge air sensor is registering false readings.

Temp Diff: The minimum supply air temperature setting (see page 15) minus the
temp diff setting represents the cold coil low temperature limit.

Lockout Delay: If the cold coil temperature drops below the low temperature limit
for the set lockout delay, the cooling loop will reference the cold coil temperature
in lieu of the discharge air sensor to prevent freeze ups.

Lockout Time: This is the amount of time the discharge air sensor will be locked
out during the cold coil protection sequence.

After three lockouts, the unit will go into alarm and the discharge air sensor will be
locked out until the alarm is cleared.

Cold Coil Protection

Temp Diff:

5.5°F

Lockout Delay:

10s

Lockout Time:

600s

T

HIS

SCREEN

ALLOWS

THE

ADJUSTMENT

OF

THE

DEFROST

CYCLE

TIMERS

.

This screen only appears if Timed Exhaust Frost Control or Energy Wheel Cycle
Frost Control was provided with the unit.

The ON/OFF times prevent the build up of frost on the energy wheel if frost
conditions are present.

Defrost Cycle Setup

Defrost minimum cycle
times.


Defrost mode:

5min

Normal mode:

30min

T

HIS

SCREEN

ALLOWS

ADJUSTMENT

OF

THE

C

OOLING

PI

CONTROL

LOOP

.

This screen only appears if cooling option was provided with the unit.

The controller utilizes a PI loop control for cooling. This allows for less sporadic
changes in supply temperature, resulting in a smooth reaction to changing
conditions. To speed up reaction time, decrease the integration time. For slower
reaction time, increase the integration time. When making adjustments, make
them in small increments and test the system to determine if the new setting is
adequate prior to further adjustment. The band is the range that the integration
will occur between.

Cooling Controller

Integration: 300s
Band: 20°F

30

DDC Controller for Tempered Air Products

®