C

OOLING

STATUS

IS

DISPLAYED

,

ALONG

WITH

COMPRESSOR

OPERATION

. (

IF

EQUIPPED

)

This screen appears if a cooling option is provided.

Chilled Water: The Cooling Control % is directly proportional to the 0-10 VDC
output signal.
0% Cooling = 0 VDC

100% Cooling = 10 VDC

The cooling control output can be configured to DIRECT / REVERSE acting,
along with the minimum and maximum output voltages by entering the
MANUFACTURER menu.

Packaged DX Cooling: The Cooling Control displays internal cooling ramp as a
percent. Compressor operation is displayed when engaged.
• D = Digital Scroll Compressor Operation
• 1 = First Staged Compressor Operation
• 2 = Second Staged Compressor Operation

Heat Pump Cooling: The Cooling Control displays internal cooling ramp as a
percent. Compressor operation is displayed when engaged.
• 1 = First Staged Compressor Operation
• 2 = Second Staged Compressor Operation

Cooling Status

Cooling Control:

000%

Compressor

D 1 2

STATUS LINE

Heating Status

Heater Control:

000%

Hot Gas Reheat:

000%

Staged reheat is:

ON

Compressor: 1

2

STATUS LINE

H

EAT

AND

REHEAT

OPERATION

IS

DISPLAYED

. (

IF

EQUIPPED

)

Heater Control displays the proportional percentage of the heater analog output.

Electric Heater: The Heater Control % is proportional to the 0-10 VDC signal
being sent to the SCR controller, located in the electric heater control center.
0% Heating = 0 VDC - 0 kW output

100% Heating = 10 VDC - Max kW output

Hot Water: The Heater Control % is proportional to the 0-10 VDC signal being
sent to the heating control valve (BY OTHERS). The heating control output can be
configured to DIRECT / REVERSE acting, along with the minimum and maximum
output voltages by entering the MANUFACTURER menu.
0% Heating = 0 VDC

100% Heating = 10 VDC

Indirect Gas: The Heater Control % is proportional to the 0-10 VDC signal being
sent to the indirect gas furnace controller, located in the indirect gas control
center. The first stage is on at 1% Heater Control. The furnace will then modulate
proportionally from minimum to maximum capacity.
0% = 0 VDC – OFF
1% = 0 VDC – MINIMUM TURNDOWN ENABLED
1 - 100% = 0 - 10 VDC = FURNACE MODULATION

Heat Pump Heating: The Heater Control % displays internal heating ramp as a
percent. Compressor operation is displayed when engaged.
• 1 = First Staged Compressor Operation
• 2 = Second Staged Compressor Operation

Hot Gas Reheat:
If hot gas reheat is staged control:
“Staged reheat is: ON/OFF” will indicate operation.

If hot gas reheat is modulating bypass damper control:
0% = OFF
1% - 100% = 4 - 10 VDC = AIRFLOW DAMPER MODULATION

If hot gas reheat is modulating valve control:
0% = OFF
1% - 100% = 0 - 10 VDC = HOT GAS REHEAT VALVE MODULATION

13