G. service – Greenheck Microprocessor Controller (475595 IOM) TAP v2.10 April 2014 (RVE, ERCH-01, ERT-01) User Manual

Page 27

background image

T

HE

P

ROBE

A

DJUSTMENT

MENU

ALLOWS

THE

USER

TO

CALIBRATE

SENSOR

PROBES

WITH

AN

OFFSET

VALUE

.

Similar screens are available for remaining sensor probes.

Analog Input

Outside Temperature

Offset: 0.0°F

Value: 70.5°F

T

HIS

SCREEN

ALLOWS

THE

USER

TO

CHANGE

THE

S

ERVICE

L

EVEL

PASSWORD

(PW1)

User Default

Insert new service password
(PW1): 1000

T

HIS

SCREEN

ALLOWS

THE

USER

TO

LOCK

THE

PROGRAM

MENU

.

Locking the program menu will prohibit users from changing any parameters.
Only menus normally accessed by pressing

Prg

will be locked. Users will still be

able to view unit status, alarms and temperatures.

Program Menu Lock

Lock program menus using
service password? (PW1): No

T

HIS

SCREEN

ALLOWS

THE

USER

TO

SAVE

AND

RESTORE

THE

DEFAULT

PARAMETERS

STORED

IN

MEMORY

.

If the user would like to save their settings, move the cursor to the SAVE position
and change to YES. This will save all of the current parameters into memory as
Service Settings. If the user would like to restore to these values at some point
in the future, moving the cursor to the RESTORE position, and selecting YES will
restore the controller to the user saved defaults.

User Default Settings

Save? No

Restore? No

T

HIS

SCREEN

ALLOWS

THE

USER

TO

VIEW

UNIT

RUN

HOURS

,

AND

ALTER

SET

POINTS

FOR

MAINTENANCE

.

Run hours: The amount of time in hours that the unit has been powered.

Set Point: The amount of running time in hours before a maintenance alarm

should occur.

Reset to Zero: Reset the measured amount of run time.

MAINTENANCE HOURS

SYSTEM

Run hours:

0000h

Set Point:

0000h

Reset to Zero?

No

The Service Settings menu allows the user to change the default Service
Password (1000), save and restore default parameters, and adjust probe values.

G.

Service

d. Service Settings

a. Working hour set

b. Probe adjustment

c. Password/Defaults

BACnet Read/Write

Function: Read

Update? Yes

*Cycle unit power to confirm
write command.

Current BACnet IP parameters should now be displayed in the BACnet TCP/IP
SETUP screen. If all values appear to be zeros, consult the factory. (Make sure you
have allowed several minutes for the controller to initialize).
*Values may appear to be zero prior to setting the Function to READ.

To change BACnet TCP/IP parameters:
1. Power on the controller and allow several minutes to initialize.
2. Go to BMS Config menu and view TCP/IP SETUP screen.
3. Move cursor to desired parameter by pressing the

buttons. Press

to select the parameter to change. Press the

buttons to adjust the

parameter. Press

to save adjusted value.

4. Once desired parameters have been entered, go to BACnet Read/Write

screen. Change Function to Write and Update? to YES.

5. Reboot the controller by cycling power to the unit. Allow several minutes for

the controller to initialize.

6. View TCP/IP parameters. If changed values did not save, contact the factory.

27

DDC Controller for Tempered Air Products

®