server facilitates commissioning and troubleshooting. Configuration is accomplished via
Ethernet. Java must be enabled in the browser used to access the BAS Remote.

Power for the BAS Remote can be derived from a 24 VAC Class 2 transformer capable
of delivering 17 VA or from a 24 VDC power supply capable of at least 10 W. Since the
unit incorporates a half-wave rectified power supply, attached I/O points and the power
supply can share a common ground. Therefore, the BAS Remote can be powered by
the same control transformer used to power other half-wave rectified control equipment.
The BAS Remote can be DIN-rail mounted into a control panel. If panel mounting is
required, use the supplied mounting tabs.

The BAS Remote conforms to the BACnet/IP standard and therefore allows field I/O to
be directly accessed via Ethernet without the need of a router. A standard web browser
with Java enabled is used for commissioning and troubleshooting. The BAS Remote
adheres to the BACnet Application Specific Controller (B-ASC) profile.