6.3.4 Current Input Configuring
You can define any channel 1
–6 as type “INPUT: 0–20 mA“ as shown in Figure 27 which uses
Channel 1 as an example. Such a channel accepts an input current in the range of 0
–20 mA.
The channel BACnet type will be Analog Input. On this screen, you can adjust any of the
following parameters.
Channel Name
You can rename the channel using no more than 63 characters.
This will be the object name for this channel (followed by the
channel number). For example, “Current Input-1”.
BACnet Unit Group
The Electrical default can be set to any option in the list.
BACnet Unit Value
The MILLIAMPERES default can be set to any option in the list. The
available options depend on the BACnet Unit Group you specify.
BACnet COV Increment Once the channel value changes by this amount (up or down), a
COV message is sent to subscribers.
BACnet Description
You can enter any string using no more than 63 characters.
ACTUAL HIGH
This specifies the highest value within the range.
ACTUAL LOW
This specifies the lowest value within the range.
SCALED HIGH
You can set a physical value corresponding to the high value.
SCALED LOW
You can set a physical value corresponding to the low value.
Figure 27
— Current Input Configuration