Contemporary Control Systems BACnet Cube I/O BMT-SI4 User Manual
Digital input module, Bmt-si4
METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany
Phone +49 7702 533-0 | Fax +49 7702 533-433
Mounting instruction see www.metz-connect.com
2. Declaration of Conformity
The device was tested according to the applicable standards. Confor-
mity was proofed. The declaration of conformity is available at the
manufacturer METZ CONNECT GmbH.
Notes Regarding Device Description
These instructions include indications for use and mounting of the
device. In case of questions that cannot be answered with these in-
structions please consult supplier or manufacturer.
The indicated installation directions or rules are applicable to the
Federal Republic of Germany. If the device is used in other countries it
applies to the equipment installer or the user to meet the
national directions.
Safety Instructions
Keep the applicable directions for industrial safety and prevention of
accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to
electrically discharge themselves as prescribed before installation or
maintenance of the devices.
Only qualified personnel shall do mounting and installation work with
the devices, see section “qualified personnel”.
The information of these instructions have to be read and
understood by every person using this device.
Symbols
Warning of dangerous electrical voltage
Danger
means that non-observance may cause risk of life,
grievous bodily harm or heavy material damage.
Qualified Personnel
Qualified personnel in the sense of these instructions are persons who
are well versed in the use and installation of such devices and whose
professional qualification meets the requirements of their work.
This includes for example:
• Qualification to connect the device according to the
VDE specifications and the local regulations and a qualification to
put this device into operation, to power it down or to activate it by
respecting the internal directions.
• Knowledge of safety rules.
• Knowledge about application and use of the device within the
equipment system etc.
7632/899299-12
Digital Input module
BMT-SI4
11088913
1. Description
The BACnet MS/TP module with 4 S0 inputs to DIN EN 62053-31
class A was developed for decentralized switching tasks. It is suitable
for counting S0 counter pulses. This allows very good integration of
the module into an energy controlling system. In case of a power
failure, the last counter readings are saved. The inputs can be scanned
by means of standard objects via a BACnet client. The module is
addressed and the baud rate is set by means of two address switches
on the front.
Suitable for decentralized mounting in serial sub-distributor.
3. Technical Data
BACnet Interface
Protocoll
BACnet MS/TP
Transmission rate
9600 ... 115200 Bd
(factory setting 9600 Bd)
Cabling
RS485 two wire bus with voltage
equalizing cable in bus / line topology
terminate with 120 Ohms
Supply
Operating voltage range
20 ... 28 V AC/DC (SELV)
Current consumption
170 mA (AC) / 65 mA (DC)
Relative duty cycle
100 %
Input
4x S0 input according to DIN EN 62053-31 Class A
Housing
Dimensions WxHxD
1.4 x 2.8 x 3.0 in. (35 x 70 x 65 mm)
Weight
83 g
Mounting position
any
Mounting
standard rail TH35 per IEC 60715
Mounting in series
the maximum quantity of modules
without space
connected in line is limited to 15 or
to a maximum power consumption of
2 Amps (AC or DC) per connection to
the power supply. For any similar
block of additional modules a sepa-
rate connection to the power supply
is mandatory.
Material
Housing
polyamide 6.6 V0
Terminal blocks
polyamide 6.6 V0
Cover plate
polycarbonate
Type of protection
(IEC 60529)
Housing
IP40
Terminal blocks
IP20
Terminal blocks
Supply and bus
4 pole terminal block
max. AWG 16 (1,5 mm²) solid wire
max. AWG 18 (1,0 mm²) stranded wire
Wire diameter
min. 0.3 mm up to max. 1.4 mm
(terminal block and jumper plug are
included to each packing unit)
Module connection
Input
max. AWG 12 (4.0 mm²) solid wire
max. AWG 14 (2.5 mm²) stranded wire
Wire diameter
min. 0.3 mm up to max 2.7 mm
Protective circuitry
polarity reversal protection of
operating voltage
polarity reversal protection of supply
and bus
Temperature range
Operation
23° F to 131° F (-5 °C to +55 °C)
Storage
-4° F to +158° F (-20 °C to +70 °C)
Display
Operating / bus activity
green LED
Error indication
red LED
Status of the inputs
yellow LED
24 V AC/DC
GND
BUS B+
BUS A-
GND
B+
A-
+24V
B+
A-
S04-
+24V
GND
S04+
S03- S03+
S01+ S01-
S02+ S02-
4. Wiring diagram
5. Wiring
MODBus RTU on RS-485
A1/ +24V
A2/ GND
BUS B +
BUS A
-
24V
RISC - CPU
Use Copper Conductors Only
24V AC / 170mA
24V DC / 65mA
GND, Class 2
S01+
S01
S04+
S04
S02+
S02
S03+
S03