beautypg.com

5 current output configuring, Current output configuring – Contemporary Control Systems BASremote User Manual (firmware 3.1.x) User Manual

Page 42

background image

TD040300-0MF

42

6.3.5 Current Output Configuring

You can define any channel 1

–6 as type “OUTPUT: 0–20 mA“ as shown in

Figure 28

which

uses Channel 1 as an example. Such a channel provides an output current in the range of 0

–20

mA. The channel BACnet type will be Analog Output. On this screen, you can adjust any of the
following parameters.

Channel Name

You can rename the channel using no more than 63 characters.
This will be the object name for this channel (followed by the
channel number). For example, “Current Input-1”.

BACnet Unit Group

The Electrical default can be set to any option in the list.

BACnet Unit Value

The MILLIAMPERES default can be set to any option in the list. The
available options depend on the BACnet Unit Group you specify.

BACnet COV Increment Once the channel value changes by this amount (up or down), a

COV message is sent to subscribers.

BACnet Description

You can enter any string using no more than 63 characters.

ACTUAL HIGH

This specifies the highest value within the range.

ACTUAL LOW

This specifies the lowest value within the range.

SCALED HIGH

You can set a physical value corresponding to the high value.

SCALED LOW

You can set a physical value corresponding to the low value.

Figure 28

— Current Output Configuration

This manual is related to the following products: