3.7 LED Indicators

LED Indicator

Indication

I/O 1

–6 configured as

Analog input

Green: > 1% of range, otherwise off

I/O 1

–6 configured as

Temperature input

Green: sensor detected

Red: open

I/O 1

–6 configured as

Contact input

Green: contact closed, otherwise off

I/O 1

–6 configured as

Pulse input

Green: pulse sensed, otherwise off

I/O 1

–6 configured as

Analog output

Green: commanded output

Red: expected output not within 40 mV on voltage or 0.2 mA on current

Status

Red: device in reset

Green flashing: booting up

Green: running application

Green flashing: Modbus serial activity after application is running

Master only

Ethernet

— Master

module only

Yellow: 10Mbps; flashes with activity

Green: 100 Mbps; flashes with activity

Network

— Expansion

module only

Green flashing: Expansion bus activity

3.8

Electromagnetic Compatibility

Standard

Test Method

Description

Test Levels

EN 55024

EN 61000-4-2

Electrostatic Discharge

6 kV contact

EN 55024

EN 61000-4-3

Radiated Immunity

10 V/m, 80 MHz to 1 GHz

EN 55024

EN 61000-4-4

Fast Transient Burst

1 kV clamp & 2 kV direct

EN 55024

EN 61000-4-5

Voltage Surge

1 kV L-L & 2 kV L-Earth

EN 55024

EN 61000-4-6

Conducted Immunity

10 V (rms)

EN 55024

EN 61000-4-11

Voltage Dips & Interruptions

1 Line cycle, 1

–5 s @100% dip

EN 55022

CISPR 22

Radiated Emissions

Class A

EN 55022

CISPR 22

Conducted Emissions

Class B

CFR 47, Part 15 ANSI C63.4

Radiated Emissions

Class A