3.7 LED Indicators
LED Indicator
Indication
I/O 1
–6 configured as
Analog input
Green: > 1% of range, otherwise off
I/O 1
–6 configured as
Temperature input
Green: sensor detected
Red: open
I/O 1
–6 configured as
Contact input
Green: contact closed, otherwise off
I/O 1
–6 configured as
Pulse input
Green: pulse sensed, otherwise off
I/O 1
–6 configured as
Analog output
Green: commanded output
Red: expected output not within 40 mV on voltage or 0.2 mA on current
Status
Red: device in reset
Green flashing: booting up
Green: running application
Green flashing: Modbus serial activity after application is running
—
Master only
Ethernet
— Master
module only
Yellow: 10Mbps; flashes with activity
Green: 100 Mbps; flashes with activity
Network
— Expansion
module only
Green flashing: Expansion bus activity
3.8
Electromagnetic Compatibility
Standard
Test Method
Description
Test Levels
EN 55024
EN 61000-4-2
Electrostatic Discharge
6 kV contact
EN 55024
EN 61000-4-3
Radiated Immunity
10 V/m, 80 MHz to 1 GHz
EN 55024
EN 61000-4-4
Fast Transient Burst
1 kV clamp & 2 kV direct
EN 55024
EN 61000-4-5
Voltage Surge
1 kV L-L & 2 kV L-Earth
EN 55024
EN 61000-4-6
Conducted Immunity
10 V (rms)
EN 55024
EN 61000-4-11
Voltage Dips & Interruptions
1 Line cycle, 1
–5 s @100% dip
EN 55022
CISPR 22
Radiated Emissions
Class A
EN 55022
CISPR 22
Conducted Emissions
Class B
CFR 47, Part 15 ANSI C63.4
Radiated Emissions
Class A