6.1.3 Accessing and Configuring the Web Server on the Master Unit
6.1.3.1
Web Browser
The Master contains an interactive web server, accessible from any Internet-compatible
PC on the local network. It is compatible with recent versions of Internet Explorer (5.0 or later,
suggested) or Netscape Navigator (7.1 or later, required). It is factory-programmed with
a default IP address of 192.168.92.68 and a Class C subnet mask of 255.255.255.0.
Once configured, changing the BAS Remote IP address is strongly encouraged.
6.1.3.2
Initial Access
The hardware arrangement for initially setting the Master
IP address appears in Figure 13. The PC should be
temporarily disconnected from the Ethernet LAN in
case the Master
’s default address matches that of a
device on the existing LAN. The procedure for altering
the IP address creates a temporary LAN composed of
nothing but the Master, the PC used to configure it and
a CAT5 cable connecting the two. Since the Master
supports Auto-MDIX, either straight-through or crossover
cable can be used.
Figure 13
— Setup for Initial IP Address
Configuration by Web Browser
For initial configuration, the PC chosen for the
procedure should temporarily have its IP address
modified as shown in Figure 14
— which employs a
Windows
®
2000 example.
Figure 14
— Steps for Changing the IP Address of the PC Used for Setup