Contemporary Control Systems BACnet Cube I/O BMT-DO4 User Manual
Digital output module bmt-do4
METZ CONNECT | Im Tal 2 | 78176 Blumberg | Germany | Phone +49 7702 533-0 | Fax +49 7702 533-433
Distributed by RIA CONNECT GmbH and BTR NETCOM GmbH
Mounting instruction see www.metz-connect.com
7605/899299-08
Digital Output Module
BMT-DO4
1108861321
2. Declaration of Conformity
The device was tested according to the applicable standards. Con-
formity was proofed. The declaration of conformity is available at
the manufacturer BTR NETCOM GmbH.
Notes Regarding Device Description
These instructions include indications for use and mounting of the
device. In case of questions that cannot be answered with these
instructions please consult supplier or manufacturer.
The indicated installation directions or rules are applicable to the
Federal Republic of Germany. If the device is used in other countries
it applies to the equipment installer or the user to meet the national
directions.
Safety Instructions
Keep the applicable directions for industrial safety and prevention of
accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to
electrically discharge themselves as prescribed before installation or
maintenance of the devices.
Only qualified personnel shall do mounting and installation work
with the devices, see section “qualified personnel”.
The information of these instructions have to be read and under-
stood by every person using this device.
Symbols
Warning of dangerous electrical voltage
Danger
means that non-observance may cause risk of life,
grievous bodily harm or heavy material damage.
Qualified Personnel
Qualified personnel in the sense of these instructions are persons
who are well versed in the use and installation of such devices and
whose professional qualification meets the requirements of their
work.
This includes for example:
• Qualification to connect the device according to the VDE
specifications and the local regulations and a qualification to put
this device into operation, to power it down or to activate it by
respecting the internal directions.
• Knowledge of safety rules.
• Knowledge about application and use of the device within the
equipment system etc.
3. Technical Data
BACnet Interface
Protocoll
BACnet MS/TP
Transmission rate
9600 to 115200 Bd
(factory setting 9600 Bd)
Cabling
RS485 two wire bus with voltage
equalizing cable in bus / line topology;
terminate with 120 Ohms
Supply
Operating voltage range
20 to 28 V AC/DC (SELV)
Current consumption
200 mA (AC) / 70 mA (DC)
Relative duty cycle
100 %
Output
Output contacts
4 x changeover contacts
Switching voltage max.
250 V AC
Continuous current max.
5 A per relay
Total current for
all contacts
12 A
Switching frequency
360 switching cycles per hour
Housing
Dimensions WxHxD
1.4 x 2.8 x 2.6 in. (35 x 70 x 65 mm)
Weight
95 g
Mounting position
any
Mounting
standard rail TH35 per IEC 60715
Mounting in series
the maximum quantity of modules
without space
connected in line is limited to 15 or
to a maximum power consumption of
2 Amps (AC or DC) per connection to
the power supply. For any similar
block of additional modules a
separate connection to the power
supply is mandatory.
Material
Housing
Polyamide 6.6 V0
Terminal blocks
Polyamide 6.6 V0
Cover plate
Polycarbonate
Type of protection
(IEC 60529)
Housing
IP40
Terminal blocks
IP20
Terminal blocks
Supply and bus
4 pole terminal block
max. AWG 16 (1.5 mm²) solid wire
max. AWG 18 (1.0 mm²) stranded wire
Wire diameter
min. 0.3 mm up to max. 1.4 mm
(terminal block and jumper plug are
included to each packing unit)
Module connection
Output
max. AWG 12 (4.0 mm²) solid wire
max. AWG 14 (2.5 mm²) stranded wire
Wire diameter
min. 0.3 mm up to max 2.7 mm
Protective circuitry
polarity reversal protection of
operating voltage
polarity reversal protection of supply
and bus
Temperature range
Operation
-5 °C to +55 °C
Storage
-20 °C to +70 °C
Display
Operating / bus activity
green LED
Error indication
red LED
Status of the outputs
yellow LED
5. Connection Diagram
BUS A-
BUS B+
14
11
12
24
21
41 44 32 31 34
42
A1
A2
A-
B+
A1
A2
A-
B+
GND
24 V AC/DC
22
4. Wiring Diagram
BUS A-
BUS B+
12 N.C.
11 C
A2 /GND
A1/+24 V
BACnet MS/TP on RS-485
RISC - CPU
24 V
14 N.O.
22 N.C.
21 C
24 N.O.
32 N.C.
31 C
34 N.O.
42 N.C.
41 C
44 N.O.
1. Description
The BACnet MS/TP module with 4 digital outputs is designed for
local switching operations. It is suitable to operate electrical
components such as motors, contactors, lamps, sun-blinds etc. We
recommend to protect the relay contacts additionally by a
RC-element or high inductive loads. The module is provided with
a manual control facility for manual switching of the relays. The
outputs can be operated by standard objects via a BACnet-Client.
Addressing of the module and baud rate setting are done with the
two address switches (x1 / x10) on the front. Possible settings are
addresses 00 to F9 and baud rates 9600 Bd, 19200 Bd, 38400 Bd,
57600 Bd, 76800 Bd and 115200 Bd.