This Object supplies the content of error register ERRCODE. Below is a list of possible error mes-
sages:
Bit
Number Designation
Explanation
0
F01*
heat sink temperature
heat sink temperature too high
limit is set by manufacturer to 80°C (176°F)
1
F02*
overvoltage
overvoltage in DC bus link
limit depends on the mains supply voltage
2
F03*
following error
message from the position controller
3
F04
feedback
cable break, short circuit, short to ground
4
F05*
undervoltage
undervoltage in DC bus link
limit is set by manufacturer to 100V
5
F06
motor temperature
motor temperature too high
limit is set by manufacturer to145°C (293°F)
6
F07
aux. voltage
internal aux. voltage not OK
7
F08*
overspeed
motor running away, speed is too high
8
F09
EEPROM
checksum error
9
F10
Flash-EPROM
checksum error
10
F11
brake
cable break, short circuit, short to ground
11
F12
motor phase
motor phase missing (cable break or similar)
12
F13*
internal temperature
internal temperature too high
13
F14
output stage
fault in the output stage
14
F15
I²t max
I²t max. value exceeded
15
F16*
supply - BTB/RTO
2 or 3 phases missing in the supply feed
16
F17
A/D converter
error in the analog-digital conversion, usually caused by excessive
EMI
17
F18
regen
regen circuit faulty or incorrect setting
18
F19*
supply phase
a supply phase is missing (can be switched off for 2-phase operati-
on)
19
F20
Slot fault
cable break, short circuit, short to ground
20
F21
Handling fault
motor phase missing (cable break or similar)
21
F22
Short circuit to earth
(ground)
AX2xxx 640/670 only: short circuit to earth (ground)
22
F23
CAN Bus off
CAN Bus total communication error
23
F24
Warning
Warning displays as error
24
F25
Commutation error
Encoder systems only
25
F26
Limit switch
Homing error (hardware limit switch reached)
26
F27
AS-option
operational error with -AS- option, input for AS-Enable and ENABLE
have been set at the same time
27
F28
reserved
reserved
28
F29
Fieldbus-Sync
Fieldbus not synchronized
29
F30
Emerg. Stop Timeout Emerg. Stop Timeout
30
F31
reserved
reserved
31
F32
System error
system software not responding correctly
* = These error messages can be cancelled by the ASCII command CLRFAULT, without executing a reset. If
only these errors are present, and the RESET button or the I/O-function RESET is used, the CLRFAULT com-
mand is also all that is carried out.