4 implementation of the stop category 1, Implementation of the stop category 1 – BECKHOFF AX2500 User Manual
Page 29

6.8.4
Implementation of the Stop Category 1
Bringing the motor to a standstill by interrupting the mains supply and using controlled
electronic braking (STOPMODE & ACTFAULT parameters set to 1). The 24 V supply
for the AX2500 must remain constant.
The drive is braked in a controlled manner during the stopping (disabling) procedure. If
the speed VEL0 (see sequence diagram in chapter 6.4) is undershot, the holding brake is
applied and the output stage is disabled.
As soon as two separate time periods (set at the time relay) have elapsed, the mains sup-
ply and the holding brake are electrically isolated.
Should an internal AX2500 fault occur, the motor is forced to a standstill once K20
drops out.
Circuit suggestion
(with EMERGENCY STOP Category 1, control function with contactor relays)
AX2500 Product Manual
29
BECKHOFF
06/2007
Technical description
AX2500
- Bus Terminal System (19 pages)
- EP-xxxx-xxxx (19 pages)
- BK2000 (30 pages)
- LC3100 (67 pages)
- BK4000 (28 pages)
- BK3xx0 (95 pages)
- BK5000 (12 pages)
- LC5200 (32 pages)
- BK7000 (29 pages)
- BK7500 (32 pages)
- BK7300 (40 pages)
- BK8100 (26 pages)
- BC2000 (28 pages)
- BC3100 (51 pages)
- BC7300 (48 pages)
- BC8100 (36 pages)
- BC3150 (112 pages)
- KL1012 (2 pages)
- KL1114 (2 pages)
- KL1164 (1 page)
- KL1232-xxxx (4 pages)
- KL1501 (19 pages)
- KL1512 (15 pages)
- KL2521-0024 (18 pages)
- KL2512 (21 pages)
- KL2612 (4 pages)
- KL2622 (9 pages)
- KL3062 (24 pages)
- KL3064 (20 pages)
- KL4132 (19 pages)
- KL4034 (25 pages)
- KL3302 (23 pages)
- KL3351 (18 pages)
- KS3681 (43 pages)
- KL4112 (18 pages)
- KL5001 (16 pages)
- KL5051 (17 pages)
- KL5101-0012 (21 pages)
- KS5111-0000 (21 pages)
- KL5121 (19 pages)
- KL6021 (20 pages)
- KL6051 (17 pages)
- Z1000 (2 pages)
- KL6071 (12 pages)
- Z1003 (2 pages)