beautypg.com

8 stop / emergency stop function to en 60204, 1 stop: standards, Stop / emergency stop function to en 60204 – BECKHOFF AX2500 User Manual

Page 26: Stop: standards

background image

6.8

Stop / Emergency Stop Function to EN 60204

6.8.1

Stop: Standards

The Stop function is used to shut down the machine in normal operation. The Stop func-
tions are defined by EN 60204 (VDE 0113), paragraphs 9.2.2 and 9.2.5.3.

Category 0:

Shut-down by immediate switching-off of the energy supply to the
drive machinery (i.e. an uncontrolled shut-down);

Category 1:

A controlled shut-down , whereby the energy supply to the drive
machinery is maintained to perform the shut-down, and the energy
supply is only interrupted when the shut-down has been completed;

Category 2:

A controlled shut-down, whereby the energy supply to the drive
machinery is maintained.

The parameters “STOPMODE” and “ACTFAULT” must be set to 1 in order to
implement the stop categories. If necessary, change the parameters via the
terminal screen of the setup software and store the data in the EEPROM.

The Stop Category must be determined by a risk evaluation of the machine. In addition,
suitable means must be provided to guarantee a reliable shut-down.

Category 0 and Category 1 Stops must be operable independently of the operating mode,
whereby a Category 0 Stop must have priority. Stop functions must be implemented by
disconnection of the appropriate circuitry, and have priority over assigned start func-
tions.

If necessary, provision must be made for the connection of protective devices and
lock-outs. If applicable, the Stop function must signal its status to the control logic. A reset
of the Stop function must not create a hazardous situation.

26

AX2500 Product Manual

Technical description

06/2007

BECKHOFF