Function blocks

78

Function blocks for TwinSAFE logic terminals

3.14.2 Signal description

Table 3-66: FB CONNECTION SHUTDOWN inputs

Name

Permitted type

Description

Deactivate1 TwinSAFE-In

FB-Out

1

st

input channel. The parameterization determines, whether the

input is linked to a normally closed contact (safe state will be
requested by logical 0) or normally open contact (safe state will be
requested by logical 1).

Deactivate2 TwinSAFE-In

FB-Out

2

nd

input channel, behaves like Deactivate1

If the discrepancy time is not equal 0, the 1

st

and 2

nd

input channel

are considered to be the 1

st

input group and a discrepancy time

monitoring is carried out between both channels, if one of the two
input channels requests the safe state.

Table 3-67: FB CONNECTION SHUTDOWN outputs

Name

Permitted type

Description

Error

TwinSAFE-Out
FB-In
Standard-Out

TRUE:
The discrepancy time monitoring for a 2-channel input group has
detected an error. The error must be acknowledged via the
ERR_ACK input of the corresponding TwinSAFE group

FALSE:
No error was found

Deactivated TwinSAFE-Out

FB-In
Standard-Out

1

st

output channel, the safe state corresponds to a logical 0.

The output is set once the connection is terminated.

Table 3-68: FB CONNECTION SHUTDOWN input and output types

Type

Description

TwinSAFE-In

TwinSAFE input at an EL1904/KL1904

Standard-In

Standard PLC variable (output in the PLC %Q*)

FB-Out

TwinSAFE FB output

TwinSAFE-Out

TwinSAFE output at an EL2904/KL2904

Standard-Out

Standard PLC variable (input in the PLC %I*)

FB-In

TwinSAFE FB input