Function blocks
68
Function blocks for TwinSAFE logic terminals
3.11.2 Signal description
Table 3-51: FB SR inputs
Name
Permitted type
Description
Set
TwinSAFE-In
FB-Out
1
st
input channel. The parameterization determines, whether the
input is linked to a normally closed contact (safe state will be
requested by logical 0) or normally open contact (safe state will be
requested by logical 1).
Reset
TwinSAFE-In
FB-Out
2
nd
input channel. The parameterization determines, whether the
input is linked to a normally closed contact (safe state will be
requested by logical 0) or normally open contact (safe state will be
requested by logical 1).
Table 3-52: FB SR outputs
Name
Permitted type
Description
SrOut
TwinSAFE-Out
FB-In
Standard-Out
1
st
output channel, the safe state corresponds to a logical 0.
3.11.2.1 FB SR input and output types
Table 3-53: FB SR input and output types
Type
Description
TwinSAFE-In
TwinSAFE input at an EL1904/KL1904
Standard-In
Standard PLC variable (output in the PLC %Q*)
FB-Out
TwinSAFE FB output
TwinSAFE-Out TwinSAFE output at an EL2904/KL2904
Standard-Out
Standard PLC variable (input in the PLC %I*)
FB-In
TwinSAFE FB input
3.11.2.2 Diagnostic and status information for FB SR
Table 3-54: Diagnostic information (16-bit value)
Index
Description
0-15
always 0
Table 3-55: Status information (8-bit value)
Index
Description
0
undefined
2
STOP
3
SAFE
9
SET