beautypg.com

BECKHOFF EL6900-FB User Manual

Page 77

background image

Function blocks

Function blocks for TwinSAFE logic terminals

75

3.13.3 FB TOF configuration in the TwinCAT System Manager

Figure 3-34: FB TOF configuration

Use the TofIn button to connect the input signal. Use the Settings button to the right of the TofIn button to
configure the input as normally open contact (NO) or normally closed contact (NC).

Use the TofOut button to connect the switch-off delayed signal.

Use the text box to set the switch-off delay time. The smallest unit is 0.1 s.

The error output is inactive since FB TOF reports no error.

The ‘MapState’ and ‘MapDiag’ checkboxes are used to specify which FB diagnostic functions are mapped
to the cyclic process image.

This manual is related to the following products: