Function blocks
74
Function blocks for TwinSAFE logic terminals
3.13.2 Signal description
Table 3-61: FB TOF inputs
Name
Permitted type
Description
TofIn1
TwinSAFE-In
FB-Out
1
st
input channel. The parameterization determines, whether the input
is linked to a normally closed contact (safe state will be requested by
logical 0) or normally open contact (safe state will be requested by
logical 1).
Table 3-62: FB TOF outputs
Name
Permitted type
Description
TofOut
TwinSAFE-Out
FB-In
Standard-Out
1
st
output channel, the safe state corresponds to a logical 0.
Table 3-63: FB TOF input and output types
Type
Description
TwinSAFE-In
TwinSAFE input at an EL1904/KL1904
Standard-In
Standard PLC variable (output in the PLC %Q*)
FB-Out
TwinSAFE FB output
TwinSAFE-Out
TwinSAFE output at an EL2904/KL2904
Standard-Out
Standard PLC variable (input in the PLC %I*)
FB-In
TwinSAFE FB input
3.13.2.1 Diagnostic and status information for FB TOF
Table 3-64: Diagnostic information (16-bit value)
Index
Description
0-15
always 0
Table 3-65: Status information (8-bit value)
Index
Description
0
undefined
1
RUN
2
STOP
3
SAFE
8
DELAY_OUT