3.13.2 Signal description

Table 3-61: FB TOF inputs

Name

Permitted type

Description

TofIn1

TwinSAFE-In
FB-Out

1

st

input channel. The parameterization determines, whether the input

is linked to a normally closed contact (safe state will be requested by
logical 0) or normally open contact (safe state will be requested by
logical 1).

Table 3-62: FB TOF outputs

Name

Permitted type

Description

TofOut

TwinSAFE-Out
FB-In
Standard-Out

1

st

output channel, the safe state corresponds to a logical 0.

Table 3-63: FB TOF input and output types

Type

Description

TwinSAFE-In

TwinSAFE input at an EL1904/KL1904

Standard-In

Standard PLC variable (output in the PLC %Q*)

FB-Out

TwinSAFE FB output

TwinSAFE-Out

TwinSAFE output at an EL2904/KL2904

Standard-Out

Standard PLC variable (input in the PLC %I*)

FB-In

TwinSAFE FB input

3.13.2.1 Diagnostic and status information for FB TOF

Table 3-64: Diagnostic information (16-bit value)

Index

Description

0-15

always 0

Table 3-65: Status information (8-bit value)

Index

Description

0

undefined

1

RUN

2

STOP

3

SAFE

8

DELAY_OUT