System description

10

Function blocks for TwinSAFE logic terminals

linked.

Apart from this the TwinSAFE group has an input (RUN), with which the processing of the assigned
function blocks can be stopped and started. All TwinSAFE group assigned outputs are in a safe state
when stopped.

2.1.1.1

TwinSAFE group inputs and outputs

Table 2-1: TwinSAFE group inputs

Name

Permitted type

Description

RUN

FB-Out

Standard-In

TRUE:

The function blocks assigned to the TwinSAFE group are executed

FALSE:

All assigned function blocks of the TwinSAFE group are at a STOP
state and thus all associated outputs are in a safe state

When the input is not linked it is in the TRUE state

ERR ACK

FB-Out

Standard-In

All pending errors in the assigned function blocks and in the
TwinSAFE connections are acknowledged by the FALSE->TRUE-
>FALSE signal sequence.

Table 2-2: TwinSAFE group outputs

Name

Permitted type

Description

FB ERR

TwinSAFE-Out

FB-In

Standard-Out

Local-Out

TRUE:

At least one assigned function block has an error

FALSE:

All assigned function blocks have no errors

COM ERR

TwinSAFE-Out

FB-In

Standard-Out

Local-Out

TRUE:

At least one TwinSAFE connection of TwinSAFE group has an error

FALSE:

All TwinSAFE connections of the TwinSAFE group have no errors

OUT ERR

TwinSAFE-Out

FB-In

Standard-Out

Local-Out

TRUE:

At least one local output assigned to the TwinSAFE group has an
error

FALSE:

All of the local outputs assigned to the TwinSAFE group have no
errors

Always FALSE for EL6900, since the device has no local outputs.