Function blocks
38
Function blocks for TwinSAFE logic terminals
Table 3-22: FB MON outputs
Name
Permitted type
Description
Error
TwinSAFE-Out
FB-In
Standard-Out
Local-Out
TRUE:
The discrepancy time monitoring of an input pair, or one of the
feedback loops, has found an error. The error reset must be
carried out via the ERR_ACK input of the related TwinSAFE
group.
FALSE:
No error was found.
MonOut
TwinSAFE-Out
FB-In
Standard-Out
Local-Out
1
st
output channel, the safe state corresponds to a logical 0.
MonDelOut
TwinSAFE-Out
FB-In
Standard-Out
Local-Out
2
nd
output channel, the safe state corresponds to a logical 0. The
safe state is output with a delay, which corresponds to the
parameterized Delay Time.
Table 3-23: FB MON input and output types
Type
Description
TwinSAFE-In
TwinSAFE input at an EL1904/KL1904
Standard-In
Standard PLC variable (output in the PLC %Q*)
FB-Out
TwinSAFE FB output
TwinSAFE-Out TwinSAFE output at an EL2904/KL2904
Standard-Out
Standard PLC variable (input in the PLC %I*)
FB-In
TwinSAFE FB input
Local-Out
TwinSAFE output at the KL6904 (not available for EL6900)
3.5.2.1
Diagnostic and status information for FB MON
Table 3-24: Diagnostic information (16-bit value)
Index
Description
0
Discrepancy error input group 1
1
Discrepancy error input group 2
2
Discrepancy error in Secure input group
4
EDM monitoring error EDM1
5
EDM monitoring error EDM2