BECKHOFF EL6900-FB User Manual
Page 17

System description
Function blocks for TwinSAFE logic terminals
15
Figure 2-6: Variables
Table 2-4: Diagnostic information for a connection
Value
Description
xxxx
0001
Invalid command
xxxx
0010
Unknown command
xxxx
0011
Invalid connection ID
xxxx
0100
Invalid CRC
xxxx
0101
Watchdog time elapsed
xxxx
0110
Invalid FSoE address
xxxx
0111
Invalid data
xxxx
1000
Invalid communication parameter length
xxxx
1001
Invalid communication parameters
xxxx
1010
Invalid user parameter length
xxxx
1011
Invalid user parameters
xxxx
1100
FSoE master reset
xxxx
1101
Module error detected on slave, with option "Module error is ComError" activated
xxxx
1110
Module error detected on EL290x, with option "Error acknowledge active" activated
xxxx
1111
Slave not yet started, or unexpected error argument
xxx
1
xxxx
FSoE slave error detected
xx
1
x
xxxx
FSoE slave reports Failsafe Value active
x
1
xx
xxxx
StartUp
1
xxx
xxxx
FSoE master reports Failsafe Value active