Function blocks

62

Function blocks for TwinSAFE logic terminals

3.9.2

Signal description

Table 3-41: FB EDM inputs

Name

Permitted type

Description

Mon1

TwinSAFE-In
FB-Out

Standard-In

1

st

input. The input can be parameterized as an normally closed

contact or an normally open contact.

Mon2

TwinSAFE-In
FB-Out

Standard-In

2

nd

input, which has to assume a value opposite to input 1 within the

set times.

Table 3-42: FB EDM outputs

Name

Permitted type

Description

Error

TwinSAFE-Out
FB-In
Standard-Out

TRUE:
SwitchOn or SwitchOff times were exceeded.

FALSE:
No error occurred.

Table 3-43: FB EDM input and output types

Type

Description

TwinSAFE-In

TwinSAFE input at an EL1904/KL1904

Standard-In

Standard PLC variable (output in the PLC %Q*)

FB-Out

TwinSAFE FB output

TwinSAFE-Out

TwinSAFE output at an EL2904/KL2904

Standard-Out

Standard PLC variable (input in the PLC %I*)

FB-In

TwinSAFE FB input

3.9.2.1

Diagnostic and status information for FB EDM

Table 3-44: Diagnostic information (16-bit value)

Index

Description

0

Switch-OFF timer elapsed

1

Switch-ON timer elapsed

Table 3-45: Status information (8-bit value)

Index

Description

0

undefined

2

STOP

4

ERROR

5

RESET

14

MON_OFF

15

MON_ON