Section 4 • ascii cross reference, Section 4, Ascii cross reference -1 – Basler Electric BE1-700 Modbus Protocol User Manual
Page 81
![background image](https://www.manualsdir.com/files/773805/content/doc081.png)
9376700991 Rev D
BE1-700 Modbus™ Protocol
4-1
SECTION 4 • ASCII CROSS REFERENCE
ASCII Command versus Modbus™ Register Cross Reference
ASCII Command
Modbus™ Registers
A=
40002-40005
CO-101
40136
CO-43
40120
CO-143
40122
CO-GROUP=
40118
CO-OUT1
40142
CO-OUT2
40144
CO-OUT3
40146
CO-OUT4
40148
CO-OUT5
40150
CO-OUTA
40140
CO-OUTALL
40138
CS-101
40135
CS-GROUP=
40117
CS-OUT1
40141
CS-OUT2
40143
CS-OUT3
40145
CS-OUT4
40147
CS-OUT5
40149
CS-OUTA
40139
CS-OUTALL
40137
EXIT
40001
GS-PWC=
40090-40093, 40094
GS-PWG=
40080-40083, 40084
GS-PWR=
40095-40098, 40099
GS-PWS=
40085-40088, 40089
M-IA
49726-49727
M-IB
49729-49730
M-IC
49732-49733
M-IG
49744-49745
M-IQ
49738-49739
M-IN
49740-47741
M-VA
49756-49757
M-VB
49758-49759
M-VC
49760-47761
M-VAB
49762-49763
M-VBC
49764-49465
M-VCA
49766-49767
M-V2
49754-49755
M-3V0
49742-49753
M-VX
49770-49771
M-V3X
49768-49769
M-FREQG
49720-49721
M-FREQB
49722-49723
M-FREQS
49724-49725
RA-MAJ
47595-47719, 40039
RA-MAJ=0
47487
RA-LGC
47595-47719, 40039
RA-LGC=0
47486
RA-MIN
47595-47719, 40039