Group setting parameters, Group setting parameters -9 – Basler Electric BE1-700 Modbus Protocol User Manual
Page 57
![background image](https://www.manualsdir.com/files/773805/content/doc057.png)
9376700991 Rev D
BE1-700 Modbus™ Protocol
3-9
Read: To read a value other than ASCII character 'X', the Select Output register must be the most
recent control register written AND must have been written within the previous 30
seconds.
P if Pulse Output selection has been made.
0 if Latch Output at 0 selection has been made.
1 if Latch Output at 1 selection has been made.
L if programmable Logic selection has been made.
E if Enable All Outputs serial control has been made.
D if Disable All Outputs serial control has been made.
X if Output control not selected or control timer has expired.
Write: The desired ASCII character.
P to select Pulsing Output.
0 to select Latching Output at 0.
1 to select Latching Output at 1.
L to select programmable Logic.
E to select Enabling All Outputs override control.
D to select Disabling All Outputs override control.
40140
Operate Output A
ASC(1)
40142
Operate Output 1
ASC(1)
40144
Operate Output 2
ASC(1)
40146
Operate Output 3
ASC(1)
40148
Operate Output 4
ASC(1)
40150
Operate Output 5
ASC(1)
Read: Current control.
P to Pulse Output.
0 to Latch Output at 0.
1 to Latch Output at 1.
L to select programmable Logic.
D if All Outputs override control Disabled
Write: The desired ASCII character to alter control (corresponding Select register must contain
same value, written within previous 30 seconds).
P to Pulse Output.
0 to Latch Output at 0.
1 to Latch Output at 1.
L to select programmable Logic.
E to Enable All Outputs override control. ∗
D to Disable All Outputs override control. ∗
∗
Requires an additional write of 'Y' to Exit register 40001 to allow these control settings to be saved to
the relay internal EEPROM.
Group Setting Parameters
40259-60
50TP Pickup
FP
40264-65
50TN Pickup
FP
40269-70
50TQ Pickup
FP
40274-75
150TP Pickup
FP
40279-80
150TN Pickup
FP
40284-85
150TQ Pickup
FP
Read and Write: 0.50 to 150.00 amps
40261-62
50TP Time Delay
LI
40266-67
50TN Time Delay
LI
40271-72
50TQ Time Delay
LI
40276-77
150TP Time Delay
LI
40281-82
150TN Time Delay
LI
40286-87
150TQ Time Delay
LI
Read and Write: 0 to 60,000 milliseconds