Global setting parameters – Basler Electric BE1-700 Modbus Protocol User Manual
Page 33
Holding
Read/Write
Data
Register
Parameter
Supported
Format
Notes
9376700991 Rev D
BE1-700 Modbus™ Protocol
2-5
40498-99
27P Pickup
R W
FP
GRP
40500-01
27P Time Delay
R W
LI
GRP
40502-03
27P Inhibit Voltage
R W
FP
GRP
40504-05
27X Pickup
R W
FP
GRP
40506-07
27X Time Delay
R W
LI
GRP
40508-09
27X Inhibit Voltage
R W
FP
GRP
40510-11
127P Pickup
R W
FP
GRP
40512-13
127P Time Delay
R W
LI
GRP
40514-15
127P Inhibit Voltage
R W
FP
GRP
40516-17
24 Pickup
R W
FP
GRP
40518-19
24 Time Delay
R W
FP
GRP
40520-21
24 Reset Delay
R W
FP
GRP
40522-23
24 Definite Timer 1 Pickup
R W
FP
GRP
40524-25
24 Definite Timer 1 Time Delay
R W
LI
GRP
40526-27
24 Definite Timer 2 Pickup
R W
FP
GRP
40528-29
24 Definite Timer 2 Time Delay
R W
LI
GRP
40530-31
24 Curve Type
R W
ASC(3)
GRP
40532-33
25 Volts
R W
FP
GRP
40534-35
25 Angle
R W
FP
GRP
40536-37
25 Slip
R W
FP
GRP
40538
25 Mode
R W
INT
GRP
40539-40
25VM Live Volts
R W
FP
GRP
40541-42
25VM Dead Volts
R W
FP
GRP
40543-44
25VM Time Delay
R W
LI
GRP
40545-46
25VM Mode1
R W
ASC(3)
GRP
40602-03
Power System Nominal Voltage
R W
FP
Global Setting Parameters
40604-05
Power System Nominal Current
R W
FP
40606-07
Breaker Fail Time Delay
R W
LI
40608-09
Programmable 51 Curve Constant A
R W
FP
40610-11
Programmable 51 Curve Constant B
R W
FP
40612-13
Programmable 51 Curve Constant C
R W
FP
40614-15
Programmable 51 Curve Constant N
R W
FP
40616-17
Programmable 51 Curve Constant R
R W
FP
40618
Input 1 Contact Recognition Time Delay
R W
SI
40619
Input 1 Contact Debounce Time Delay
R W
SI
40620
Input 2 Contact Recognition Time Delay
R W
SI
40621
Input 2 Contact Debounce Time Delay
R W
SI
40622
Input 3 Contact Recognition Time Delay
R W
SI
40623
Input 3 Contact Debounce Time Delay
R W
SI
40624
Input 4 Contact Recognition Time Delay
R W
SI
40625
Input 4 Contact Debounce Time Delay
R W
SI
40746-870
Contiguous Poll Block Assignments
R W
INT
40871
Setting Group Control On Time
R W
INT