9376700991 Rev D
BE1-700 Modbus™ Protocol
3-5
Bit 1 - 159X tripped
Bit 0 - 59X tripped
Bit 0 - 159 phase tripped
Logic Term Count
Term Count Register
SI
0
means the logic equation is disabled (NONE)
-1
means the logic equation consists of a single term of OR-ed variables
1
means the logic equation consists of a single term of AND-ed variables
2
means the logic equation consists of the OR-ing of 2 terms of AND-ed variables
3
means the logic equation consists of the OR-ing of 3 terms of AND-ed variables
4
means the logic equation consists of the OR-ing of 4 terms of AND-ed variables
Session Parameters
40001
Exit
ASC(1)
Read: Always the ASCII character '0' (zero)
Write: ASCII characters 'Y' or 'N' ('Y' to save changes, 'N' to ignore changes)
Note 1: ERROR DETAIL block (49835-54) contains Exit status message following a write.
Note 2: Writing to this register is effective only when Password Security register 40989 is
enabled.
40002-5
Access Password
ASC(8)
Read: Always the ASCII string of '*' characters.
Write: Access password in ASCII string.
Note 1: If password written is less than 8 characters long, a binary zero value must be
included following the final password character.
Note 2: Writing to this register is effective only when Password Security register 40989 is
enabled.
40006
Access Request
BM(16)
Read: Returns the current write access available to the Modbus user
Bit 3 is set for Global Access
Bit 2 is set for Setting Access
Bit 1 is set for Control Access
Bit 0 is set for Report Access
Zero value for Read Only Access
Write: To request write privileges using the password written into Access Password registers.
Value written into Access Request register is arbitrary (any value will initiate the request).
Note 1: If write access is denied, the response message will be an error response
message with Illegal Function exception code.
Step1. Write the desired password to PASSWORD registers 40002 to 40005
Step2. Write any value to ACCESS REQUEST register 40006
Step3. Read Access Level from ACCESS REQUEST register 40006
Note 2: Writing to this register is effective only when Password Security register 40989 is
enabled.
Template Parameters
40036
Settings Group Selection
SI
Read: Returns the current value of Settings Group Selection.
Write: The desired value to assign a Settings Group to the Group (GRP) Template.
O for Settings Group 0
1 for Settings Group 1
40038
Fault Selection
SI
Read: Returns the current value of Fault Selection.
Write: The desired value to assign a Fault Record to the Fault (FLT) Template. Allowed values
are 1 - 255.
Note: Refer to Fault Indicator (47512) and Fault Template Status (47513) Registers.