Basler Electric BE1-700 Modbus Protocol User Manual
Page 59
![background image](https://www.manualsdir.com/files/773805/content/doc059.png)
9376700991 Rev D
BE1-700 Modbus™ Protocol
3-11
40429-30
27R Pickup
FP
Read and Write: 30.0 to 250
40431
27R Control Mode
ASC(1)
Read and Write: R or C
40432-33
47 Pickup
FP
Read and Write: 1 to 300
40434-35
47 Time Delay
LI
Read and Write 50 to 600,000 milliseconds
40436-37
59P Pickup
FP
40440-41
59X Pickup
FP
40444-45
159P Pickup
FP
40448-49
159X Pickup
FP
Read and Write: 10.0 to 300
40438-39
59P Time Delay
LI
40442-43
59X Time Delay
LI
40446-47
159P Time Delay
LI
40450-51
159X Time Delay
LI
Read and Write 50 to 600,000 milliseconds
40460-61
81 Pickup
FP
40465-66
181 Pickup
FP
40470-71
281 Pickup
FP
40475-76
381 Pickup
FP
40480-81
481 Pickup
FP
40485-86
581 Pickup
FP
Read and Write: 40.00 to 70.00 Hz
40462-63
81 Time Delay
LI
40467-68
181 Time Delay
LI
40472-73
281 Time Delay
LI
40477-78
381 Time Delay
LI
40482-83
481 Time Delay
LI
40487-88
581 Time Delay
LI
Read and Write: 0 to 600,000 milliseconds
40464
81 Mode
ASC(1)
40469
181 Mode
ASC(1)
40474
281 Mode
ASC(1)
40479
381 Mode
ASC(1)
40484
481 Mode
ASC(1)
40489
581 Mode
ASC(1)
Read and Write: O = overfrequency, U = underfrequency
R = Rate of Change
40490-91
81 Phase A Voltage Inhibit Setting
FP
Read and Write: 15.0 to 150 volts
40492-93
81 Neg-Seq. Voltage Inhibit Setting
FP
Read and Write: 0 to 99% of Phase A Inhibit Setting
40494-95
81 Overfrequency Inhibit Setting
FP
40496-97
81 Underfrequency Inhibit Setting
FP
Read and Write: 46.0 to 64.0 Hz