Basler Electric BE1-700 Modbus Protocol User Manual
Page 64

3-16
BE1-700 Modbus™ Protocol
9376700991 Rev D
41265-66
Major Alarm Mask MSBs
BM(16)
41267-68
Minor Alarm Mask MSBs
BM(16)
41269-70
Logic Alarm Mask MSBs
BM(16)
Read and Write:
Bit 15 - Spare
Bit 14 - Volts per Hertz alarm
Bit 13 - 60 Fuse Loss alarm
Bit 12 - Changes Lost alarm
Bit 11 - Freq Range alarm
Bit 10 - Spare
Bit 9 - Spare
Bit 8 - Logic = None alarm
Bit 7 - Flt Rpt Timeout alarm
Bit 6 - Virtual Output 15 alarm
Bit 5 - Virtual Output 14 alarm
Bit 4 - Virtual Output 13 alarm
Bit 3 - Setting Group Change Active alarm
Bit 2 - Loss of IRIG-B sync or IRIG-B decode problem
Bit 1 - An override is active in one or more outputs
Bit 0 - EEPROM Non fatal error
41266
Major Alarm Mask LSBs
BM(16)
41268
Minor Alarm Mask LSBs
BM(16)
41270
Logic Alarm Mask LSBs
BM(16)
Read and Write:
Bit 15 - User settings changed ('EXIT' with 'Y')
Bit 14 - Power reset alarm, hard reset of MPU
Bit 13 - Clock problem, real time clock has not been set
Bit 12 - Communicating failure alarm, read error on serial port
Bit 11 - Operating System Overload detected alarm
Bit 10 - Setting group override in effect
Bit 9 - Q demand alarm, excessive negative-sequence unbalance
Bit 8 - Neutral demand alarm
Bit 7 - Phase demand alarm
Bit 6 - Breaker alarm #3
Bit 5 - Breaker alarm #2
Bit 4 - Breaker alarm #1
Bit 3 - Recloser Lockout
Bit 2 - Recloser Fail
Bit 1 - Breaker fail alarm
Bit 0 - Out 1 CKT Open alarm
41272
Clock Format - Date
ASC(1)
Read and Write: M for mm/dd/yy format, D for dd/mm/yy format
41273
Clock Format - Time
SI
Read and Write: 12 for 12 hour clock, 24 for 24 hour clock
41274
Clock Format - Daylight Savings
SI
Read and Write: 0 for disabling Daylight Savings, 1 for enabling Daylight Savings
41275
Phase Demand Interval
SI
41276
Neutral Demand Interval
SI
41277
Negative-Sequence Demand Interval
SI
Read and Write: 1 to 60 minutes, 0 to disable
41281
LCD Backlight Timer
INT
Read and Write: 1 to 600 seconds, 0 for “always on”