Introduction, Logic settings, Logic modes – Basler Electric BE1-700 Modbus Protocol User Manual
Page 49: Section 3 • register details -1, Introduction -1, Logic settings -1, Logic modes -1
![background image](https://www.manualsdir.com/files/773805/content/doc049.png)
9376700991 Rev D
BE1-700 Modbus™ Protocol
3-1
SECTION 3 • REGISTER DETAILS
Introduction
This section details the register formats and data ranges of the previous section. The two sections
combined provide all information necessary to communicate with the BE1-700 Modbus™ Holding
Registers.
Any Holding Register not listed in the Register Table is an unassigned Holding Register. A value of zero
always results when reading an unassigned Holding Register. Writes to unassigned Holding Registers are
legal but no action will be taken (that is, the write is ignored).
Logic Settings
Logic settings consist of a combination of modes, masks, terms, and term counts. Logic modes are
specific to each logic set, while the masks, terms, and term counts have value definitions consistent
throughout all logic sets. A single logic equation consists of a "mask" and "term" pair. The logic "term
count" is used only in VOA, VO1-VO15 virtual output logic blocks.
The logic "mode" enables or disables the logic equation for that logic block.
The logic "mask" corresponds to the System Status bits to be evaluated. These bits are referenced in the
desired logic equation and are set to 1 (non-used bits masked out as 0's).
The logic "term" corresponds to the System Status bit's TRUE or FALSE state, referenced in the desired
logic equation where only the TRUE bits in the equation are set to 1.
he logic "term count" may be of one of four logic types which are NONE (logic disabled), OR only ( a + b +
c), AND only (a * b * c) or MIXED (a * b + b * c).
The following defines all logic set parameters.
Logic Modes
41505
Programmable 50TP Logic Mode
INT
41539
Programmable 50TQ Logic Mode
INT
41556
Programmable 150TP Logic Mode
INT
41590
Programmable 150TQ Logic Mode
INT
Read and Write:
0 for disabled
1 for enabled
41522
Programmable 50TN Logic Mode
INT
41573
Programmable 150TN Logic Mode
INT
Read and Write:
0 for disabled
1 for calculated neutral
2 for measured ground
41658
Programmable Breaker Fail Logic Mode
INT
Read and Write:
0 for disabled
1 for enabled
41691
Programmable 51P Logic Mode
INT
41725
Programmable 51Q Logic Mode
INT
41708
Programmable 51N Logic Mode
INT
41759
Programmable 151N Logic Mode
INT
Read and Write:
0 for disabled
1 for calculated neutral
2 for measured ground