Basler Electric BE1-700 Modbus Protocol User Manual
Page 75

9376700991 Rev D
BE1-700 Modbus™ Protocol
3-27
47472
Peak Demand Since Reset Timestamp - day
INT
47477
Peak Demand Since Reset Timestamp - day
INT
47482
Peak Demand Since Reset Timestamp - day
INT
Read only: Any value (days since 01/01/1984)
47463-64
Peak Demand Since Reset Timestamp - millisecond
LI
47468-69
Peak Demand Since Reset Timestamp - millisecond
LI
47473-74
Peak Demand Since Reset Timestamp - millisecond
LI
47478-79
Peak Demand Since Reset Timestamp - millisecond
LI
47483-84
Peak Demand Since Reset Timestamp - millisecond
LI
Read only: 0 to 86,399,999 milliseconds
47486
Reset Logic Alarm Information
SI
47487
Reset Major Alarm Information
SI
47488
Reset Minor Alarm Information
SI
47489
Reset Relay Alarm Information
SI
47491
Clear Fault Log
SI
47492
Trigger Fault Record
SI
47493
Clear Events Report
SI
Read: 0
Write: Any value will perform reset / trigger / clear.
47512
Fault Indicator
SI
Read only: Most recent Fault number (1 - 255)
47513
Fault Template Status
SI
Read only:
0: Template not valid for current Fault Selection (Refer to Register 40038). All FLT
template values will read 0.
1 to 255: Valid user selected Fault Number.
The following is the Fault Template (RPT):
47514
Fault Date and Time – day
INT
Read only: Any value (days since 01/01/1984).
47515-16
Fault Date and Time – milliseconds
LI
Read only: 0 to 86,399,999 milliseconds
47517
Fault Event Type
BM(16)
Read only:
Bit 0 for Breaker Fail
Bit 1 for Trip
Bit 2 for Logic
Bit 3 for Pickup
Bit 4 for Fault Record Trigger (Refer to Register 47492)
47518
Fault Active Group
SI
Read only: 0 to 1
47519
Fault Targets MSBs
BM(16)
Read only:
Bit 15 - Spare
Bit 14 - Spare
Bit 13 - Spare
Bit 12 - 51C
Bit 11 - 51B
Bit 10 - 51A
Bit 9 - 150TQ
Bit 8 - 50TQ
Bit 7 - 150TN