BE1-700 Modbus™ Protocol
9376700991 Rev D
40273
50TQ Directional Mode
ASC(1)
40278
150TP Directional Mode
ASC(1)
40283
150TN Directional Mode
ASC(1)
40288
150TQ Directional Mode
ASC(1)
Read and Write:
R = Reverse
N = Neutral
F = Forward
40301-02
51P Pickup
FP
40308-09
51N Pickup
FP
40315-16
51Q Pickup
FP
40329-30
151N Pickup
FP
Read and Write: 0.50 to 16.00 amps
40303-04
51P Time Dial
FP
40310-11
51N Time Dial
FP
40317-18
51Q Time Dial
FP
40331-32
151N Time Dial
FP
Read and Write: 0.0 to 9.9
40305-06
51P Curve Type
ASC(3)
40312-13
51N Curve Type
ASC(3)
40319-20
51Q Curve Type
ASC(3)
40333-34
151N Curve Type
ASC(3)
Read and Write: one of the following ASCII strings
S1, S2, L1, L2, D, M, I1, I2, V1, V2, E1, E2, S1R, S2R, L1R, L2R, DR, MR, I1R, I2R,
V1R, V2R, E1R, E2R, A, B, C, G, F, P, AR, BR, CR, GR, FR, PR, 46, 46R
40307
51P Directional Mode
ASC(1)
40314
51N Directional Mode
ASC(1)
40321
51Q Directional Mode
ASC(1)
40335
151N Directional Mode
ASC(1)
Read and Write:
R = reverse
N = neutral
F = forward
40359-60
62 Time Delay 1
LI
40361-62
62 Time Delay 2
LI
40363-64
162 Time Delay 1
LI
40365-66
162 Time Delay 2
LI
Read and Write: 0 to 9,999,000 milliseconds
40406-07
79 First Automatic Reclose Delay
LI
40408-09
79 Second Automatic Reclose Delay
LI
40410-11
79 Third Automatic Reclose Delay
LI
40412-13
79 Fourth Automatic Reclose Delay
LI
40414-15
79 Reset Time Delay
LI
40416-17
79 Reclose Fail Time Delay
LI
40418-19
79 Maximum Reclose Time
LI
40420-21
79 Pilot Time Delay
LI
Read and Write: 100 to 600,000 milliseconds, 0 to disable
40422
79 Sequence Control
BM(16)
Read and Write:
Bit 0 to Block Shot #1
Bit 1 to Block Shot #2
Bit 2 to Block Shot #3
Bit 3 to Block Shot #4
Bit 4 to Block Shot #5