BE1-700 Modbus™ Protocol
3-13
Global Setting Parameters
40602-03
Power System Nominal Voltage
FP
Read and Write: 50 to 250
40604-05
Power System Nominal Current
FP
Read and Write: 0.5 to 10.0
40606-07
Breaker Fail Time Delay
LI
Read and Write: 50 to 999 milliseconds, 0 to disable
40608-09
Programmable 51 Curve Constant A Delay
FP
Read and Write: 0.0000 to 600.0000
40610-11
Programmable 51 Curve Constant B Delay
FP
Read and Write: 0.0000 to 25.0000
40612-13
Programmable 51 Curve Constant C Delay
FP
Read and Write: 0.0000 to 1.0000
40614-15
Programmable 51 Curve Constant N Delay
FP
Read and Write: 0.5000 to 2.5000
40616-17
Programmable 51 Curve Constant R Delay
FP
Read and Write: 0.0000 to 30.0000
40618
Input 1 Contact Recognition Time Delay
SI
40619
Input 1 Contact Debounce Time Delay
SI
40620
Input 2 Contact Recognition Time Delay
SI
40621
Input 2 Contact Debounce Time Delay
SI
40622
Input 3 Contact Recognition Time Delay
SI
40623
Input 3 Contact Debounce Time Delay
SI
40624
Input 4 Contact Recognition Time Delay
SI
40625
Input 4 Contact Debounce Time Delay
SI
Read and Write: 4 to 255 milliseconds
40746-870
Contiguous Poll Block Assignments
INT
Read and Write:
0 if Unassigned
1 to 9874: Holding Register 40001 to 49874
40871
Setting Group Control On Time
INT
Read and Write: 0 to 10 seconds
40872
Setting Group 1 Automatic Control Switch Time
SI
40874
Setting Group 1 Automatic Control Return Time
SI
Read and Write: 0 to 60 minutes
40873
Setting Group 1 Automatic Control Switch Level
SI
40875
Setting Group 1 Automatic Control Return Level
SI
Read and Write: 0 to 150%
40876
Setting Group 1 Tracking Element
INT
Read and Write: 0 to 8 (0 = 51P, 1 = 51Q, 2 = 51N, 3 = 151N, 4 = 791, 5 = 792, 6 = 793, 7 = 794,
8 =60FL)
40903-04
60FL Loss of Current Auto Block Setting
ASC(3)
Read and Write: ENA/DIS
40905-06
60FL Loss of Voltage Auto Block Setting
ASC(3)
Read and Write: DIS/ PNQ/ PN/ PQ/ NQ/ P/ N/ Q
Serial Port Setting Parameters
40962
Serial Port 0 Baud Rate
INT
40980
Serial Port 2 Baud Rate
INT
Read and Write:
0 - 300 baud (Do not select for Port 2 Modbus communications)
1 - 600 Baud (Do not select for Port 2 Modbus communications)