Basler Electric BE1-700 Modbus Protocol User Manual
Page 69

9376700991 Rev D
BE1-700 Modbus™ Protocol
3-21
47370
System Status (Logic Var 48 to 63)
BM(16)
Read only:
Bit 15 - Target Reset key
Bit 14 - Output circuit monitor
Bit 13 - Alarm minor
Bit 12 - Alarm major
Bit 11 - Alarm logic
Bit 10 - 101 SC
Bit 9 - 101C
Bit 8 - 101T
Bit 7 - 27X picked-up
Bit 6 - 27X tripped
Bit 5 - 162
Bit 4 - 62
Bit 3 - Input 4 status
Bit 2 - Input 3 status
Bit 1 - Input 2 status
Bit 0 - Input 1 status
47371
System Status (Logic Var 64 to 79)
BM(16)
Read only:
Bit 15 - 59 phase tripped
Bit 14 - BF tripped
Bit 13 - BF picked up
Bit 12 - 24 picked up
Bit 11 - 24 tripped
Bit 10 - 47 picked-up
Bit 9 - 47 tripped
Bit 8 - 127 phase picked-up
Bit 7 - 27 phase picked-up
Bit 6 - 127 phase tripped
Bit 5 - 27 phase tripped
Bit 4 - 159 phase picked-up
Bit 3 - 59 phase picked-up
Bit 2 - Settings Group 1
Bit 1 - Settings Group 0
Bit 0 - Alarm Reset key
47372
System Status (Logic Var 80 to 95)
BM(16)
Read only:
Bit 15 - Spare
Bit 14 - Spare
Bit 13 - 25 tripped
Bit 12 - 25 Voltage Monitor 1
Bit 11 - 60FL
Bit 10 - 581 tripped
Bit 9 - 481 tripped
Bit 8 - 381 tripped
Bit 7 - 281 tripped
Bit 6 - 181 tripped
Bit 5 - 81 tripped
Bit 4 - 159X picked-up
Bit 3 - 59X picked-up
Bit 2 - 159X tripped
Bit 1 - 59X tripped
Bit 0 - 159 phase tripped
47373
Current Active Group Setting
SI
Read only: 0 or 1