Basler Electric BE1-700 Modbus Protocol User Manual
Page 60
![background image](https://www.manualsdir.com/files/773805/content/doc060.png)
3-12
BE1-700 Modbus™ Protocol
9376700991 Rev D
40498-99
27P Pickup
FP
40510-11
127P Pickup
FP
Read and Write: 10.0 to 300
40504-05
27X Pickup
FP
Read and Write: 1.00 to 150
40500-01
27P Time Delay
LI
40506-07
27X Time Delay
LI
40512-13
127P Time Delay
LI
Read and Write: 50 to 600,000 milliseconds
40502-03
27P Inhibit Voltage
FP
40514-15
127P Inhibit Voltage
FP
Read and Write: 10.0 to 300
40508-09
27X Inhibit Voltage
FP
Read and Write: 1.00 to 150
40516-17
24 Pickup
FP
Read and Write: 0.50 to 6.00
40518-19
24 Time Delay
FP
40520-21
24 Reset Delay
FP
Read and Write: 0 to 9.9
40522-23
24 Definite Timer 1 Pickup
FP
40526-27
24 Definite Timer 2 Pickup
FP
Read and Write: 0.50 to 6.00
40524-25
24 Definite Timer 1 Time Delay
FP
40528-29
24 Definite Timer 2 Time Delay
FP
Read and Write: 50 to 600000
40530-31
24 Curve Type
ASC(3)
Read and Write: 0.5, 1 or 2
40532-33
25 Delta Volts
FP
Read and Write: 1.0 to 20.0
40534-35
25 Phase Angle
FP
Read and Write: 1 to 45
40536-37
25 Slip Frequency
FP
Read and Write: 0 to 0.5 Hz
40538
25 Mode
LI
Read and Write: 1 = GF>BF, 0 = GF<>BF
40539-40
25 VM Live Volts
FP
40541-42
25 VM Dead Volts
FP
Read and Write: 10.0 to 150
40543-44
25 VM Time Delay
LI
Read and Write: 50 to 60,000 milliseconds
40545-46
25 VM Mode 1
ASC(3)
Read and Write: 1,2, and/or 3, DIS