Global parameters, Global parameters -6, Table 3-1. report – Basler Electric BE1-700 Modbus Protocol User Manual
Page 54

3-6
BE1-700 Modbus™ Protocol
9376700991 Rev D
40039
Report Selection
SI
Read: Returns the current value of Report Selection.
Writing to Report Selection terminates previous report and initializes new report. See the
table for values.
40040
Report Focus
INT
Read: Returns the current value of Report Focus.
Write: See Table 3-1 for values.
Note: If an illegal Report Focus value is written, the user is not notified until a read of the
Report Text is attempted.
Note: Write to Report Selection and Report Focus to specify the report which will be
made available via the Report (RPT) Template. The template is the Report Text Block at
47595-719.
Table 3-1. Report
Report Text
47595-719
Report Selection
40039
Report Focus
40040
RA-LGC Report
0
Not used
RA-MAJ Report
1
Not used
RA-MIN Report
2
Not used
RA-REL Report
3
Not used
RF Report
4
Not used
RF-# Report
5
Value of # (1 – 255)
RF-NEW Report
6
Not used
RS Report
7
Not used
RS-# Report
8
Value of # (1 - 255)
RS-NEW Report
9
Not used
RS-F# Report
10
Value of # (1 – 255)
RS-ALM
11
Not used
RS-IO
12
Not used
RS-LGC
13
Not used
Global Parameters
Global Parameter registers 40080 - 40099 are effective only for serial communication ports active with
ASCII protocol and for the Modbus serial port, COM2, when Password Security register 40989 is enabled.
40080-83
Global Password
ASC(8)
40085-88
Setting Password
ASC(8)
40090-93
Control Password
ASC(8)
40095-98
Report Password
ASC(8)
Read: If global access granted, password ASCII strings are read. Otherwise, the ASCII string of
'*' characters is read.
Write: Password in ASCII string.
Note: If password written is less than 8 characters long, a binary zero value must be
included following the final password character.
40084
Global Path
BM(8)
40089
Setting Path
BM(8)
40094
Control Path
BM(8)
40099
Report Path
BM(8)
Read: Path associated with password
Write: Path associated with password
Bit 2 is set for COM 2 access.
Bit 1 is set for COM1 access.
Bit 0 is set for COM0 / FP access.