Metering parameters, Metering parameters -30 – Basler Electric BE1-700 Modbus Protocol User Manual
Page 78
![background image](https://www.manualsdir.com/files/773805/content/doc078.png)
3-30
BE1-700 Modbus™ Protocol
9376700991 Rev D
47529-30
Fault Breaker Operate Time
FP
Read only:
0 if Fault Breaker Operate Time Status is not 0 (not valid)
Time (xxx.xxx) in seconds if Fault Breaker Operate Time Status is 0 (valid).
47532-33
Fault Phase A Current Magnitude
FP
47535-36
Fault Phase B Current Magnitude
FP
47538-39
Fault Phase C Current Magnitude
FP
47541-42
Fault Residual Current Magnitude
FP
Read only: Value in amps.
47546-47
Fault Phase A Voltage Magnitude
FP
47548-49
Fault Phase B Voltage Magnitude
FP
47550-51
Fault Phase C Voltage Magnitude
FP
47552-53
Fault Neutral Voltage Magnitude
FP
Read only: Value in volts.
47556-57
Fault Generator Frequency
FP
47558-59
Fault Bus Frequency
FP
Read only: Value in Hz.
The following is the Report Template (RPT).
47595-719
Report Text
Read only: ASCII string (Illegal message response generated for invalid Report Focus value).
Metering Parameters
49719
Part Number
INT
Read only: 0 to 999
49720-21
Generator Frequency
FP
49722-23
Bus Frequency
FP
49724-25
Slip Frequency
FP
Read only: Value in hertz
49726-27
Phase A Current Magnitude
FP
49729-30
Phase B Current Magnitude
FP
49732-33
Phase C Current Magnitude
FP
49738-39
Negative-Sequence Current Magnitude
FP
49740-41
Neutral Current Magnitude
FP
49744-45
Ground Current Magnitude
FP
Read only: Value in amps. If not applicable, reads undefined floating point value of 0xFFFFFFFF.
49742-43
Zero-Sequence Voltage
FP
49754-55
Negative-Sequence Voltage
FP
49756-57
Phase A Voltage
FP
49758-59
Phase B Voltage
FP
49760-61
Phase C Voltage
FP
49762-63
Phase A-B Voltage
FP
49764-65
Phase B-C Voltage
FP
49766-67
Phase C-A Voltage
FP
49768-69
V3x Voltage
FP
49770-71
Bus Voltage
FP
Read only: Value in volts. If not applicable, reads undefined floating point value of 0xFFFFFFFF. *
Value in KVA
49772-73
Slip Angle
FP
Read only: Value in degrees