Basler Electric BE1-700 Modbus Protocol User Manual
Page 56

3-8
BE1-700 Modbus™ Protocol
9376700991 Rev D
40135
Select 101 Virtual Breaker Control Switch
ASC(1)
Read: To read a value other than ASCII character 'X,' the Select 101 Virtual Breaker Control
Switch register must be the most recent control register written AND must have been
written within the previous 30 seconds.
C if Close selection has been made.
T if Trip selection has been made.
X if 101 Virtual Breaker Control Switch control not selected or control timer has expired.
Write: The desired ASCII character.
C to select Closing the Switch.
T to select Tripping the Switch.
40136
Operate 101 Virtual Breaker Control Switch
ASC(1)
Read: Current control.
C if Close Switch.
T if Trip Switch.
Write: The desired ASCII character to alter control (corresponding Select register must contain
same value, written within previous 30 seconds).
C to Close Switch.
T to Trip Switch.
40137
Select All Outputs
ASC(1)
Read: To read a value other than ASCII character 'X,' the Select All Output register must be the
most recent control register written AND must have been written within the previous 30
seconds.
P if Pulse All Outputs selection has been made.
0 if Latch All Outputs at 0 selection has been made.
1 if Latch All Outputs at 1 selection has been made.
L if programmable Logic selection has been made.
E if Enable All Outputs override control has been set.
D if Disable All Outputs override control has been set.
X if All Outputs control not selected or control timer has expired.
Write: The desired ASCII character.
P to select Pulsing All Outputs.
0 to select Latching All Outputs at 0.
1 to select Latching All Outputs at 1.
L to select programmable Logic.
E to select Enabling All Outputs override control.
D to select Disabling All Outputs override control.
40138
Operate All Outputs
ASC(1)
Read: Current control.
E if All Outputs override control Enabled.
D if All Outputs override control Disabled.
Write: The desired ASCII character to alter control (corresponding Select register must contain
same value, written within previous 30 seconds).
P to Pulse All Outputs.
0 to Latch All Outputs at 0.
1 to Latch All Outputs at 1.
L to select programmable Logic.
E to Enable All Outputs override control. ∗
D to Disable All Outputs override control. ∗
40139
Select Output A
ASC(1)
40141
Select Output 1
ASC(1)
40143
Select Output 2
ASC(1)
40145
Select Output 3
ASC(1)
40147
Select Output 4
ASC(1)
40149
Select Output 5
ASC(1)