beautypg.com

AMETEK CSW Series User Manual

Page 34

background image

User Manual

California Instruments

34

CSW Series


C

OLUMN

1:

SIZE

(AWG)

C

OLUMN

2:

AMPERES

(MAXIMUM)

C

OLUMN

3:

OHMS/100 FEET

(ONE WAY)

C

OLUMN

4:

IR DROP/100 FEET

(COL. 2 X COL. 3)

14

15

0.257

3.85

12

20

0.162

3.24

10

30

0.102

3.06

8

40

0.064

2.56

6

55

0.043

2.36

4

70

0.025

1.75

2

95

0.015

1.42

1/0

125

0.010

1.25

3/0

165

0.006

1.04

Recommended Wire Gauge Selection Guide

The output power cables must be large enough to prevent a total voltage drop exceeding 1% of
the rated output voltage between the power source and the load. Table 3-1 shows the AWG size
of the cables that may be used. Cable lengths must not exceed twenty-five (25) feet. For lengths
greater than 25 feet, calculate the voltage drop from the following formula:

2 X DISTANCE X CABLE RESISTANCE PER FT. X CURRENT = VOLT DROP


LOAD CURRENT

WIRE GAGE

22 AMPS

10 AWG

37 AMPS

8 AWG

74 AMPS

4 AWG

111 AMPS

2 AWG

Table 3-1: Wire Sizes